Wiring
FP0
7
−
20
7.9
Wiring the RS232C Port
7.9
Wiring the RS232C Port
When using the RS232C port, use the screw-down connection type terminal and the
wire according to the following procedures.
Item
Specification
Baud rate
300/600/1200/2400/4800/
9600/19200 bps
Transmission
distance
3m/9.84 ft.
Terminal block
Made by Phoenix Contact
Co. (3-pin)
Product number: MKDS
1/3-3.5
Communication
method
half-duplex
Settings when shipped from the factory
These are changed using system registers
412 to 414. The settings in effect when the
unit is shipped from the factory are noted
below.
412
RS232C port is not used.
413
Character bit: 8 bits
Parity check: odd
Stop bit: 1 bit
Header: without STX code
Terminator: CR
414
Baud rate: 9600 bps
Suitable wires (twisted wire)
−
Size: AWG #28 to 16
−
Conductor cross-sectional area: 0.08 to 1.25 mm
2
Use a shielded wire of the above wiring. We recommend grounding the shield section.
Also, if using a pole terminal, see
*
section 7.6.
RS232C port
terminal layout
SG: Signal Ground
RD: Receive Data
SD: Send Data
FP0 Control unit with RS232C port
(FP0 C10CRM/C10CRS/C14CRM/C14CRS/C16CT/C16CP/C32CT/C32CP)
Summary of Contents for FP0 Series
Page 14: ...Table of Contents FP0 xii ...
Page 16: ...Overview FP0 1 2 ...
Page 82: ...S LINK Control Unit FP0 4 2 ...
Page 95: ...Chapter 5 I O Allocation 5 1 I O Number 5 3 5 2 Control Unit 5 4 5 3 Expansion I O Unit 5 5 ...
Page 96: ...I O Allocation FP0 5 2 ...
Page 100: ...I O Allocation FP0 5 6 5 3 Expansion I O Unit ...
Page 102: ...Installation FP0 6 2 ...
Page 112: ...Installation FP0 6 12 6 5 Installation Using FP0 Flat Type Mounting Plate ...
Page 114: ...Wiring FP0 7 2 ...
Page 198: ...High speed Counter Pulse Output PWM Output FP0 9 34 9 5 PWM Output Function ...
Page 200: ...General use Serial Communications FP0 10 2 ...
Page 210: ...Self Diagnostic and Troubleshooting FP0 11 2 ...
Page 220: ...Specifications FP0 12 2 ...
Page 234: ...Dimensions FP0 13 2 ...
Page 243: ...Chapter 14 Appendix ...
Page 380: ...14 138 14 7 ASCII Codes ...