Self-Diagnostic and Troubleshooting
FP0
11
−
6
11.2 Troubleshooting
Error code is 20 or higher
A self-diagnostic error other than a syntax error has occurred.
<Condition>
Using FP programmer
II
Press the keys as shown on the right.
Error code 43 and higher can be cleared.
Use the programming tool in PROG. mode to clear the error.
<Procedure 1 >
Using FPWIN GR
Click the “Clear Error” button in the status display menu described on the previ-
ous page.
In the PROG. mode, the power supply can be turned OFF and then ON
again to clear the error, but all of the contents of the operation memory
except hold type data are cleared.
An error can also be cleared by executing a self
−
diagnostic error set
instruction
F148 (ERR)
.
Follow the procedures described in the table of error codes.
<Procedure 2 >
Note
When an operation error (error code 45) occurs, the address at
which the error occurred is stored in special data registers
DT9017 and DT9018. If this happens, monitor the address at
which the error occurred before cancelling the error.
Summary of Contents for FP0 Series
Page 14: ...Table of Contents FP0 xii ...
Page 16: ...Overview FP0 1 2 ...
Page 82: ...S LINK Control Unit FP0 4 2 ...
Page 95: ...Chapter 5 I O Allocation 5 1 I O Number 5 3 5 2 Control Unit 5 4 5 3 Expansion I O Unit 5 5 ...
Page 96: ...I O Allocation FP0 5 2 ...
Page 100: ...I O Allocation FP0 5 6 5 3 Expansion I O Unit ...
Page 102: ...Installation FP0 6 2 ...
Page 112: ...Installation FP0 6 12 6 5 Installation Using FP0 Flat Type Mounting Plate ...
Page 114: ...Wiring FP0 7 2 ...
Page 198: ...High speed Counter Pulse Output PWM Output FP0 9 34 9 5 PWM Output Function ...
Page 200: ...General use Serial Communications FP0 10 2 ...
Page 210: ...Self Diagnostic and Troubleshooting FP0 11 2 ...
Page 220: ...Specifications FP0 12 2 ...
Page 234: ...Dimensions FP0 13 2 ...
Page 243: ...Chapter 14 Appendix ...
Page 380: ...14 138 14 7 ASCII Codes ...