Wiring
FP0
7
−
5
7.2 Wiring the Power Supply to the Control Unit
7.2
Wiring the Power Supply to the Control Unit
Use the power supply cable (AFP0581) that comes with the unit to connect the power
supply.
Power supply
cable
(AFP0581)
Green:
Function earth
Blue: 0 V
Brown:
24 V DC
FP0 control unit
Power supply
connector
Item
Descriptions
Rated voltage
24 V DC
Operating voltage range
21.6 to 26.4 V DC
Notes
To minimize adverse effects from noise, twist the brown and
blue wires of the power supply cable.
To protect the system against erroneous voltage from the
power supply line, use an insulated power supply with an
internal protective circuit.
The regulator on the FP0 unit is a non-insulated type.
If using a power supply device without an internal protective
circuit, always make sure power is supplied to the unit
through a protective element such as a fuse.
next page
Summary of Contents for FP0 Series
Page 14: ...Table of Contents FP0 xii ...
Page 16: ...Overview FP0 1 2 ...
Page 82: ...S LINK Control Unit FP0 4 2 ...
Page 95: ...Chapter 5 I O Allocation 5 1 I O Number 5 3 5 2 Control Unit 5 4 5 3 Expansion I O Unit 5 5 ...
Page 96: ...I O Allocation FP0 5 2 ...
Page 100: ...I O Allocation FP0 5 6 5 3 Expansion I O Unit ...
Page 102: ...Installation FP0 6 2 ...
Page 112: ...Installation FP0 6 12 6 5 Installation Using FP0 Flat Type Mounting Plate ...
Page 114: ...Wiring FP0 7 2 ...
Page 198: ...High speed Counter Pulse Output PWM Output FP0 9 34 9 5 PWM Output Function ...
Page 200: ...General use Serial Communications FP0 10 2 ...
Page 210: ...Self Diagnostic and Troubleshooting FP0 11 2 ...
Page 220: ...Specifications FP0 12 2 ...
Page 234: ...Dimensions FP0 13 2 ...
Page 243: ...Chapter 14 Appendix ...
Page 380: ...14 138 14 7 ASCII Codes ...