Installation
FP0
6
−
7
6.2 Important Notes
Installation space
−
Leave at least 50 mm/1.97 in. of space between the wiring
ducts of the unit and other devices to allow heat radiation
and unit replacement.
50 mm/1.97 in. or more
50 mm/1.97 in. or more
FP0
−
Maintain a minimum of 100 mm/3.937 in. between devices to
avoid adverse affects from noise and heat when installing a
device or panel door to the front of the FP0 unit.
100mm/3.937 in.
or more
Other device or panel door
FP0
−
Keep the first 100 mm/3.937 in. from the front surface of the
FP0 control unit open in order to allow room for
programming tool connections and wiring.