14-131
Error
code
Name
Opera-
tion
status
Description and steps to take
FP0
FP-e
FP
Σ
FP-X
FP1/FP-M
FP2
FP2SH
FP10SH
FP3
Selec-
table
S-LINK error Occurs only in FP0-SL1
When one of the S-LINK errors (ERR1, 3
or 4) has been deteced,error code E46
(remote I/O (S-LINK) communication
error) is stored.
Selection of operation status using
system register27:
-to continue operation,set K1
-to stop operation,set K0
A
E46
Remote
I/O
commu-
nication
error
Selec-
table
MEWNET-F communication error
A communication abnormally was
caused by a transmission cable or during
the power-down of a slave station.
FP2, FP2SH, and FP10SH:
Check the contents of special data
registers DT90131 to DT90137 and
locate the abnormal slave station and
recover the communication condition.
FP3:
Check the contents of special data
registers DT9131 to DT9137 and locate
the abnormal slave station and recover
the communication condition.
Selection of operation status using
system register27:
-to continue operation,set K1
-to stop operation,set K0
A
A
A
A
A
E47
MEW-NET-
F
attribute
error
Selec-
table
In the unit on the slave station, an
abnormallty such as:
-missing unit
-abnormal intelligent unit was detected.
FP2, FP2SH, and FP10SH:
Check the contents of special data
registers DT90131 to DT90137 and
locate the abnormal slave station and
recover the slave condition.
FP3:
Check the contents of special data
registers DT9131 to DT9137 and locate
the abnormal slave station and recover
the slave condition.
Selection of operation status using
system register28:
-to continue operation,set 1
-to stop operation,set 0
A
A
A
A
E49
Expansion
unit power
supply
sequence
error
Stops
The power supply for the expansion unit
was turned on after the control unit.
Turn on the power supply for the
expansion unit at the same time or
before the control unit is turend on.
A
A:Available
Summary of Contents for FP0 Series
Page 14: ...Table of Contents FP0 xii ...
Page 16: ...Overview FP0 1 2 ...
Page 82: ...S LINK Control Unit FP0 4 2 ...
Page 95: ...Chapter 5 I O Allocation 5 1 I O Number 5 3 5 2 Control Unit 5 4 5 3 Expansion I O Unit 5 5 ...
Page 96: ...I O Allocation FP0 5 2 ...
Page 100: ...I O Allocation FP0 5 6 5 3 Expansion I O Unit ...
Page 102: ...Installation FP0 6 2 ...
Page 112: ...Installation FP0 6 12 6 5 Installation Using FP0 Flat Type Mounting Plate ...
Page 114: ...Wiring FP0 7 2 ...
Page 198: ...High speed Counter Pulse Output PWM Output FP0 9 34 9 5 PWM Output Function ...
Page 200: ...General use Serial Communications FP0 10 2 ...
Page 210: ...Self Diagnostic and Troubleshooting FP0 11 2 ...
Page 220: ...Specifications FP0 12 2 ...
Page 234: ...Dimensions FP0 13 2 ...
Page 243: ...Chapter 14 Appendix ...
Page 380: ...14 138 14 7 ASCII Codes ...