Precautions During Programming
FP0
8
−
17
8.5 Instruction of Leading Edge Detection Method
Example 2:
Using the CT instruction between JP and LBL instructions
LBL 1
R0
JP
1
X0
X1
100
CT
R0
X0
R0
X0
Counting
operation
Time chart 2
Counting
operation
Time chart 1
Final timing at
which the
previous
JP
instruction was
not executed
The count is not incremented, because the final
timing at which the previous
JP
instruction was not
executed has not been changed, and the execution
condition X0 for the counter input has not changed.
Final timing at
which the
previous
JP
instruction
was not
executed
The count is incremented, because the count input
changed from off to on after the final timing at which
the previous
JP
instruction was not executed.
Summary of Contents for FP0 Series
Page 14: ...Table of Contents FP0 xii ...
Page 16: ...Overview FP0 1 2 ...
Page 82: ...S LINK Control Unit FP0 4 2 ...
Page 95: ...Chapter 5 I O Allocation 5 1 I O Number 5 3 5 2 Control Unit 5 4 5 3 Expansion I O Unit 5 5 ...
Page 96: ...I O Allocation FP0 5 2 ...
Page 100: ...I O Allocation FP0 5 6 5 3 Expansion I O Unit ...
Page 102: ...Installation FP0 6 2 ...
Page 112: ...Installation FP0 6 12 6 5 Installation Using FP0 Flat Type Mounting Plate ...
Page 114: ...Wiring FP0 7 2 ...
Page 198: ...High speed Counter Pulse Output PWM Output FP0 9 34 9 5 PWM Output Function ...
Page 200: ...General use Serial Communications FP0 10 2 ...
Page 210: ...Self Diagnostic and Troubleshooting FP0 11 2 ...
Page 220: ...Specifications FP0 12 2 ...
Page 234: ...Dimensions FP0 13 2 ...
Page 243: ...Chapter 14 Appendix ...
Page 380: ...14 138 14 7 ASCII Codes ...