Precautions During Programming
FP0
8
−
9
8.3 Handling Index Registers
R0
DF
F81 BIN, WX1, IX
1
2
F81 BIN, WX0, IXSV0
1
Convert the BCD timer number data in WX1 to binary and
set it in index register IX.
2
Convert the BCD timer set value in WX0 to binary and
stored in the timer set value area SV specified by contents
of IX.
Example 2: External output of the elapsed value in a timer number specified
by a digital switch
1
PLC
WX1
7-segmenet
indicator
WY0
R1
DF
F81 BIN, WX1, IX
1
2
F80 BCD, IXEV0, WY0
Timer elapsed
value display
Digital
switches
Timer
number
setting
1
Convert the BCD timer number data in WX1 to binary, and
set it in index register IX.
2
Convert the elapsed value data EV in the timer specified by
IX to BCD, and output it to word external output relay WY0.
Summary of Contents for FP0 Series
Page 14: ...Table of Contents FP0 xii ...
Page 16: ...Overview FP0 1 2 ...
Page 82: ...S LINK Control Unit FP0 4 2 ...
Page 95: ...Chapter 5 I O Allocation 5 1 I O Number 5 3 5 2 Control Unit 5 4 5 3 Expansion I O Unit 5 5 ...
Page 96: ...I O Allocation FP0 5 2 ...
Page 100: ...I O Allocation FP0 5 6 5 3 Expansion I O Unit ...
Page 102: ...Installation FP0 6 2 ...
Page 112: ...Installation FP0 6 12 6 5 Installation Using FP0 Flat Type Mounting Plate ...
Page 114: ...Wiring FP0 7 2 ...
Page 198: ...High speed Counter Pulse Output PWM Output FP0 9 34 9 5 PWM Output Function ...
Page 200: ...General use Serial Communications FP0 10 2 ...
Page 210: ...Self Diagnostic and Troubleshooting FP0 11 2 ...
Page 220: ...Specifications FP0 12 2 ...
Page 234: ...Dimensions FP0 13 2 ...
Page 243: ...Chapter 14 Appendix ...
Page 380: ...14 138 14 7 ASCII Codes ...