14-122
14.4 Table of Error codes
Difference in ERROR display
There are differences in the way errors are displayed depending on the model.
Model
Display
Display method
FP1,FP-M,FP2,FP3,FP10SH LED
ERROR. Continually
lit
FP
Σ
,FP0, FP-X
LED
ERROR/ALARM Flashes/contunually
lit
FP-e
Screen display
ERR.
Continually lit
Error Confirmation When ERROR Turns ON
When the “ERROR” on the control unit (CPU unit) turns on or flashes, a self-diagnostic error or syntax
check error has occurred. Confirm the contents of the error and take the appopriate steps.
-Error Confirmation Method
Procedure:1.Use the programming tool software to call up the error code.
By executing the “STATUS DISPLAY”, the error code and content of error are
displayed.
2.Check the error contents in the table of error codes using the error code
ascertained above.
-Syntax check error
This is an error detected by the total check function when there is a syntax error or incorrect setting
written in the program. When the mode selector is switched to the RUN mode, the total check function
automatically activates and eliminates the possibility of incorrect operation from syntax errors in the
program.
When a syntax check error is detected
-ERROR turns on or flashes.
-Operation will not begin even after swirching to the RUN mode.
-Remote operation cannot be used to change to RUN mode.
Clearing a syntax check error
By changing to the PROG.mode, the error will clear and the ERROR will turn off.
Steps to take for syntax error
Change to the PROG. mode, and then execute the total check function while online mode with the
programming tool connected. This will call up the content of error and the address where the error
occurred.
Correct the program while referring to the content of error.
Summary of Contents for FP0 Series
Page 14: ...Table of Contents FP0 xii ...
Page 16: ...Overview FP0 1 2 ...
Page 82: ...S LINK Control Unit FP0 4 2 ...
Page 95: ...Chapter 5 I O Allocation 5 1 I O Number 5 3 5 2 Control Unit 5 4 5 3 Expansion I O Unit 5 5 ...
Page 96: ...I O Allocation FP0 5 2 ...
Page 100: ...I O Allocation FP0 5 6 5 3 Expansion I O Unit ...
Page 102: ...Installation FP0 6 2 ...
Page 112: ...Installation FP0 6 12 6 5 Installation Using FP0 Flat Type Mounting Plate ...
Page 114: ...Wiring FP0 7 2 ...
Page 198: ...High speed Counter Pulse Output PWM Output FP0 9 34 9 5 PWM Output Function ...
Page 200: ...General use Serial Communications FP0 10 2 ...
Page 210: ...Self Diagnostic and Troubleshooting FP0 11 2 ...
Page 220: ...Specifications FP0 12 2 ...
Page 234: ...Dimensions FP0 13 2 ...
Page 243: ...Chapter 14 Appendix ...
Page 380: ...14 138 14 7 ASCII Codes ...