14-116
Num-
ber
Name Boolean
Operand
Description
Steps
F338
P338
Floating-
point type
data radian
→
degree
DEG
PDEG
S, D
The angle data in radians (real number data)
specified in (S+1, S) is converted to angle data in
degrees, and the result is stored in (D+1, D).
8
Floating-point type real number data processing instructions
F345
P345
Floating-
point type
data compare
FCMP
PFCMP
S1, S2
(S1+1, S1)>(S2+1, S2)
→
R900A: on
(S1+1, S1)=(S2+1, S2)
→
R900B on
(S1+1, S1)<(S2+1, S2)
→
R900C: on
10
F346
P346
Floating-
point type
data band
compare
FWIN
PFWIN
S1, S2, S3
(S1+1, S1)>(S3+1, S3)
→
R900A: on
(S2+1, S2)<or =(S1+1, S1)<or =(S3+1, S3)
→
R900B on
(S1+1, S1)<(S2+1, S2)
→
R900C: on
14
F347
P347
Floating-
point type
data upper
and lower
limit control
FLIMT
PFLIMT
S1, S2, S3,
D
When (S1+1, S1)>(S3+1, S3), (S1+1, S1)
→
(D+1, D)
When (S2+1, S2)<(S3+1, S3), (S2+1, S2)
→
(D+1, D)
When (S1+1, S1)<or = (S3+1, S3)<or =(S2+1, S2),
(S3+1, S3)
→
(D+1, D)
17
F348
P348
Floating-
point type
data dead-
band control
FBAND
PFBAND
S1, S2, S3,
D
When (S1+1, S1)>(S3+1, S3),
(S3+1, S3)
−
(S1+1, S1)
→
(D+1, D)
When (S2+1, S2)<(S3+1, S3),
(S3+1, S3)
−
(S2+1, S2)
→
(D+1, D)
When (S1+1, S1)<or = (S3+1, S3)<or =(S2+1, S2),
0.0
→
(D+1, D)
17
F349
P349
Floating-
point type
data zone
control
FZONE
PFZONE
S1, S2, S3,
D
When (S3+1, S3)<0.0,
(S3+1, S3)+(S1+1, S1)
→
(D+1, D)
When (S3+1, S3)=0.0, 0.0
→
(D+1, D)
When (S3+1, S3)>0.0, (S3+1, S3)+(S2+1, S2)
→
(D+1, D)
17
F350
P350
Floating-
point type
data maxi-
mum value
FMAX
PFMAX
S1, S2, D
Searches the maximum value in the real number
data table between the area selected with “S1” and
“S2”, and stores it in the (D+1, D). The address
relative to “S1” is stored in (D+2).
8
Summary of Contents for FP0 Series
Page 14: ...Table of Contents FP0 xii ...
Page 16: ...Overview FP0 1 2 ...
Page 82: ...S LINK Control Unit FP0 4 2 ...
Page 95: ...Chapter 5 I O Allocation 5 1 I O Number 5 3 5 2 Control Unit 5 4 5 3 Expansion I O Unit 5 5 ...
Page 96: ...I O Allocation FP0 5 2 ...
Page 100: ...I O Allocation FP0 5 6 5 3 Expansion I O Unit ...
Page 102: ...Installation FP0 6 2 ...
Page 112: ...Installation FP0 6 12 6 5 Installation Using FP0 Flat Type Mounting Plate ...
Page 114: ...Wiring FP0 7 2 ...
Page 198: ...High speed Counter Pulse Output PWM Output FP0 9 34 9 5 PWM Output Function ...
Page 200: ...General use Serial Communications FP0 10 2 ...
Page 210: ...Self Diagnostic and Troubleshooting FP0 11 2 ...
Page 220: ...Specifications FP0 12 2 ...
Page 234: ...Dimensions FP0 13 2 ...
Page 243: ...Chapter 14 Appendix ...
Page 380: ...14 138 14 7 ASCII Codes ...