F0 MV, H 112, DT 100
R31
DF
X1
R30
R30
F0 MV, K 200, DT 101
F0 MV, K4000, DT 102
F0 MV, K 250, DT 103
F1 DMV, K22000, DT 104
F0 MV, K 0, DT 106
R903A
R32
DF
R30
R31
F168 SPD1, DT 100, H 0
DF/
R903A
R32
R32
R30
T2
Positioning operations running
Positioning operations start
Positioning completion pulse (1 s)
TMX 2, K10
High
−
speed Counter/Pulse Output/ PWM Output
FP0
9
−
28
9.4
Pulse Output Function
Absolute value positioning operation
When X1 is turned on, pulses are output from Y0. If the current value at that point is
larger than ”22,000”, the direction output Y2 goes on, and if the value is smaller than
”22,000”, the direction output Y2 does not go on.
DT100
Control code: H112
[refer to “instruction
F168 (SPD1)
”]
DT101
Initial speed: 200 Hz
DT102
Maximum speed:
4000 Hz
DT103
Acceleration/decelera-
tion time: 250 ms
DT104
DT105
Target value: 22000
DT106
Pulse stop
(
−
side)
(+ side)
(10,000)
22,000
(30,000)
Motor
250 ms
250 ms
4000 Hz
200 Hz
0 Hz
Regardless of the current value, its movement
is towards position “22,000.”
Summary of Contents for FP0 Series
Page 14: ...Table of Contents FP0 xii ...
Page 16: ...Overview FP0 1 2 ...
Page 82: ...S LINK Control Unit FP0 4 2 ...
Page 95: ...Chapter 5 I O Allocation 5 1 I O Number 5 3 5 2 Control Unit 5 4 5 3 Expansion I O Unit 5 5 ...
Page 96: ...I O Allocation FP0 5 2 ...
Page 100: ...I O Allocation FP0 5 6 5 3 Expansion I O Unit ...
Page 102: ...Installation FP0 6 2 ...
Page 112: ...Installation FP0 6 12 6 5 Installation Using FP0 Flat Type Mounting Plate ...
Page 114: ...Wiring FP0 7 2 ...
Page 198: ...High speed Counter Pulse Output PWM Output FP0 9 34 9 5 PWM Output Function ...
Page 200: ...General use Serial Communications FP0 10 2 ...
Page 210: ...Self Diagnostic and Troubleshooting FP0 11 2 ...
Page 220: ...Specifications FP0 12 2 ...
Page 234: ...Dimensions FP0 13 2 ...
Page 243: ...Chapter 14 Appendix ...
Page 380: ...14 138 14 7 ASCII Codes ...