Wiring
FP0
7
−
14
7.6
Wiring the Terminal Type
7.6
Wiring the Terminal Type
A screw-down connection type terminal block socket for terminal of FP0 control unit and
analog I/O unit is used. The terminal block socket and suitable wires are given below.
Terminal block socket
Suitable wire
Terminal block socket
Item
Description
Manufacturer
Phoenix Contact Co.
Model
MC1,5/9-ST-3,5
Product number
1840434
Suitable wires (twisted wire)
Item
Description
Control unit
Size: AWG #24 to 16
Conductor cross-sectional area: 0.3 to 1.25 mm
2
Analog I/O unit
Size: AWG #28 to 16
g /
Conductor cross-sectional area: 0.08 to 1.25 mm
2
Pole terminal with a compatible insulation sleeve
If a pole terminal is being used, the following models are marketed by Phoenix Contact
Co.
Manufacturer
Cross-sectional
area (mm
2
)
Size
Product number
Phoenix Contact Co.
0.25
AWG #24
AI 0,25
−
6YE
0.50
AWG #20
AI 0,5
−
6WH
0.75
AWG #18
AI 0,75
−
6GY
1.00
AWG #18
AI 1
−
6RD
Pressure welding tool for pole terminals
Manufacturer
Phoenix Contact Co.
Type
CRIMPFOX UD6
Product number
12 04 43 6
When tightening the terminals of the terminal block socket, use a screwdriver (Phoenix
Contact Co., Product no. 1205037) with a blade size of 0.4
×
2.5. The tightening torque
should be 0.22 to 0.25 N
⋅
m (2.3 to 2.5 kgf
⋅
cm) or less.
Summary of Contents for FP0 Series
Page 14: ...Table of Contents FP0 xii ...
Page 16: ...Overview FP0 1 2 ...
Page 82: ...S LINK Control Unit FP0 4 2 ...
Page 95: ...Chapter 5 I O Allocation 5 1 I O Number 5 3 5 2 Control Unit 5 4 5 3 Expansion I O Unit 5 5 ...
Page 96: ...I O Allocation FP0 5 2 ...
Page 100: ...I O Allocation FP0 5 6 5 3 Expansion I O Unit ...
Page 102: ...Installation FP0 6 2 ...
Page 112: ...Installation FP0 6 12 6 5 Installation Using FP0 Flat Type Mounting Plate ...
Page 114: ...Wiring FP0 7 2 ...
Page 198: ...High speed Counter Pulse Output PWM Output FP0 9 34 9 5 PWM Output Function ...
Page 200: ...General use Serial Communications FP0 10 2 ...
Page 210: ...Self Diagnostic and Troubleshooting FP0 11 2 ...
Page 220: ...Specifications FP0 12 2 ...
Page 234: ...Dimensions FP0 13 2 ...
Page 243: ...Chapter 14 Appendix ...
Page 380: ...14 138 14 7 ASCII Codes ...