14-104
Num-
ber
Name Boolean
Operand
Description
Steps
F277
P277
Sort (word
data (16-bit))
SORT
PSORT
S1, S2, S3
The word data with sign from the area specified by
“S1” to “S2” are sorted in ascending order (the
smallest word is first) or descending order (the
largest word is first).
8
F278
P278
Sort (double
word data
(32-bit))
DSORT
PDSORT
S1, S2, S3
The double word data with sign from the area
specified b “S1” ato “S2” are sorted in ascending
order (the smallest word is first) or descending
order (the largest word is first).
8
F282
P282
Scaling of
16-bit data
SCAL
PSCAL
S1, S2, D
The toutptu value Y is found for the input value X
by performing scaling for the given data table.
8
F283
P283
Scaling of
32-bit data
DSCAL
PDSCAL
S1, S2, D
The toutptu value Y is found for the input value X
by performing scaling for the given data table.
10
F284
P284
Inclination
output of 16-
bit data
RAMP
S1, S2, S3,
D
Executes the linear output for the specified time
from the specified initial value to the target value.
10
Integer type non-linear function instructions
F285
P285
Upper and
lower limit
control
(16-bit data)
LIMT
PLIMT
S1, S2, S3,
D
When S1>S3, S1
→
D
When S1<S3, S2
→
D
When S1<or = S3<or = S2, S3
→
D
10
F286
P286
Upper and
lower limit
control
(32-bit data)
DLIMT
PDLIMT
S1, S2, S3,
D
When (S1+1, S1)>(S3+1, S3), (S1+1, S1)
→
(D+1, D)
When (S2+1, S2)<(S3+1, S3), (S2+1, S2)
→
(D+1, D)
When (S1+1, S1)<or = (S3+1, S3)<or = (S2+1, S2),
(S3+1, S3)
→
(D+1, D)
16
F287
P287
Deadband
control
(16-bit data)
BAND
PBAND
S1, S2, S3,
D
When S1>S3, S3
−
S1
→
D
When S2<S3, S3
−
S2
→
D
When S1<or = S3<or = S2, 0
→
D
10
F288
P288
Deadband
control
(32-bit data)
DBAND
PDBAND
S1, S2, S3,
D
When (S1+1, S1)>(S3+1, S3), (S3+1, S3)
−
(S1+1,
S1)
→
(D+1, D)
When (S2+1, S2)<(S3+1, S3), (S3+1, S3)
−
(S2+1,
S2)
→
(D+1, D)
When (S1+1, S1)<or = (S3+1, S3)<or = (S2+1,
S2),0
→
(D+1, D)
16
F289
P289
Zone control
(16-bit data)
ZONE
PZONE
S1, S2, S3,
D
When S3<0, S3+S1
→
D
When S3=0, 0
→
D
When S3>0, S3+S2
→
D
10
F290
P290
Zone control
(32-bit data)
DZONE
PDZONE
S1, S2, S3,
D
When (S3+1, S3)<0, (S3+1, S3)+(S1+1, S1)
→
(D+1, D)
When (S3+1, S3)=0, 0
→
(D+1, D)
When (S3+1, S3)>0, (S3+1, S3)+(S2+1, S2)
→
(D+1, D)
16
Summary of Contents for FP0 Series
Page 14: ...Table of Contents FP0 xii ...
Page 16: ...Overview FP0 1 2 ...
Page 82: ...S LINK Control Unit FP0 4 2 ...
Page 95: ...Chapter 5 I O Allocation 5 1 I O Number 5 3 5 2 Control Unit 5 4 5 3 Expansion I O Unit 5 5 ...
Page 96: ...I O Allocation FP0 5 2 ...
Page 100: ...I O Allocation FP0 5 6 5 3 Expansion I O Unit ...
Page 102: ...Installation FP0 6 2 ...
Page 112: ...Installation FP0 6 12 6 5 Installation Using FP0 Flat Type Mounting Plate ...
Page 114: ...Wiring FP0 7 2 ...
Page 198: ...High speed Counter Pulse Output PWM Output FP0 9 34 9 5 PWM Output Function ...
Page 200: ...General use Serial Communications FP0 10 2 ...
Page 210: ...Self Diagnostic and Troubleshooting FP0 11 2 ...
Page 220: ...Specifications FP0 12 2 ...
Page 234: ...Dimensions FP0 13 2 ...
Page 243: ...Chapter 14 Appendix ...
Page 380: ...14 138 14 7 ASCII Codes ...