Wiring
FP0
7
−
7
7.3
Grounding
7.3
Grounding
Under normal conditions, the inherent noise resistance is sufficient. However, in
situations of excess noise, ground the instrument to increase noise suppression.
For grounding purposes, use wiring with a
minimum of 2 mm
2
. The grounding
connection should have a resistance of
less than 100
Ω
.
FP0
FP0
CORRECT
Other
device
Other
device
Notes
The point of grounding should be as close to the FP0 control
unit as possible. The ground wire should be as short as
possible.
If two devices share a single ground point, it may produce an
adverse effect. Always use an exclusive ground for each
device.
Depending on the surroundings in which the equipment is
used, grounding may cause problems.
<Example>
Since the power supply line (24 VDC and GND terminal) of the
FP0 power supply connector is connected to the frame ground
(F.G.) through a varistor, if there is an irregular potential
between the power supply line (24 VDC and GND) and earth,
the varistor may be shorted.
24 V DC
GND
F.G.
Varistor
Varistor (39 V DC)
Power supply lines
Power supply connector
of FP0 control unit
Summary of Contents for FP0 Series
Page 14: ...Table of Contents FP0 xii ...
Page 16: ...Overview FP0 1 2 ...
Page 82: ...S LINK Control Unit FP0 4 2 ...
Page 95: ...Chapter 5 I O Allocation 5 1 I O Number 5 3 5 2 Control Unit 5 4 5 3 Expansion I O Unit 5 5 ...
Page 96: ...I O Allocation FP0 5 2 ...
Page 100: ...I O Allocation FP0 5 6 5 3 Expansion I O Unit ...
Page 102: ...Installation FP0 6 2 ...
Page 112: ...Installation FP0 6 12 6 5 Installation Using FP0 Flat Type Mounting Plate ...
Page 114: ...Wiring FP0 7 2 ...
Page 198: ...High speed Counter Pulse Output PWM Output FP0 9 34 9 5 PWM Output Function ...
Page 200: ...General use Serial Communications FP0 10 2 ...
Page 210: ...Self Diagnostic and Troubleshooting FP0 11 2 ...
Page 220: ...Specifications FP0 12 2 ...
Page 234: ...Dimensions FP0 13 2 ...
Page 243: ...Chapter 14 Appendix ...
Page 380: ...14 138 14 7 ASCII Codes ...