A - 33
A Appendix
GX-series EtherCAT Slave Unit User’s Manual
A-1 Obje
ct Diction
ary
A
A-1
-7 Manufa
ctur
er Specific Objects
•
Object mounted only on Slave Units operating in the DC mode.
•
The number of sequences for detecting communications errors is set with this object.
•
The setting range is from 00 to 0F hex and the number of detections is "the set number of times + 1."
•
Rewriting value is possible at operation in the DC mode, but the operation is performed with the value
set when shifting from the pre-operational state to safe-operational state. Note that at this point, the
rewritten value is read.
Note: With the default setting of 01 hex, an error is detected if communications errors occur twice in a row.
Precaution for Safe Use
When using the cable redundancy in DC Mode, the Communications Error Setting set value for
EtherCAT Slave Units in DC Mode should be set to "1" (default value) or higher. If the
communications cable is disconnected or the power supply of the EtherCAT Slave Units is
turned OFF with the Communications Error Setting set value set to "0", communications may
discontinue.
•
Object mounted only on Slave Units operating in the DC mode.
•
This object is used to set the standby time until the first synchronization interrupt signal (SYNC0) is
input after shifting to the safe-operational state (state where a DC mode is confirmed).
•
If the first interrupt signal (SYNC0) is not input at all within this setting time, a synchronization error
occurs.
•
The setting range is from 0000 hex to 0258 hex (600s) and operation is performed at 120s when
0000 hex is set.
•
Rewriting value is possible at operation in the DC mode, but the operation is performed with the value
set when shifting from the pre-operational state to safe-operational state. Note that at this point, the
rewritten value is read.
2200 hex
Communication Error Setting
Range: 00 hex to 0F hex
Unit: number of
sequences
Default: 01 hex
Attribute: C*
Size: 1 byte (U8)
Access: RW
PDO map: Not possible
2201 hex
Sync Not Received Timeout Setting
Range: 0000 hex to 0258 hex
Unit: s
Default: 0000 hex
Attribute: C*
Size: 2 bytes (U16)
Access: RW
PDO map: Not possible
Summary of Contents for GX-AD0471
Page 3: ...GX series EtherCAT Slave Units User s Manual Revised October 2018...
Page 4: ......
Page 42: ...2 EtherCAT Slave Unit 2 8 GX series EtherCAT Slave Unit User s Manual...
Page 66: ...4 Installation and Wiring 4 18 GX series EtherCAT Slave Unit User s Manual...
Page 84: ...5 EtherCAT Communications 5 18 GX series EtherCAT Slave Unit User s Manual...
Page 98: ...6 Basic Specifications of Slave Units 6 14 GX series EtherCAT Slave Unit User s Manual...
Page 178: ...7 Digital I O Slave Unit 7 80 GX series EtherCAT Slave Unit User s Manual...
Page 206: ...8 Analog I O Slave Unit 8 28 GX series EtherCAT Slave Unit User s Manual...
Page 280: ...11 Expansion Unit 11 20 GX series EtherCAT Slave Unit User s Manual...
Page 388: ...A Appendix A 84 GX series EtherCAT Slave Unit User s Manual...
Page 392: ...Revision 2 GX series EtherCAT Slave Unit User s Manual...
Page 393: ......