12 Troubleshooting and Maintenance
12 - 4
GX-series EtherCAT Slave Unit User’s Manual
Errors of EtherCAT Network
[PWR]
indicator
[L/A IN]
[L/A OUT]
LED
[RUN]
indicator
[ERR]
indicator
Description
Cause
Actions
On
On
−
−
Link
established in
physical layer
Operation standby
status after
establishing link in
physical layer.
−
On
Off
−
−
Link not
established in
physical layer
A link in physical
layer has not been
established.
After checking the
following items, restart
the Slave Unit according
to the specification of
connected EtherCAT
Master Unit.
•
Is the
communications
cable wired correctly?
•
Are any cables
disconnected or loose
in the part that
connects to the
connector?
•
Is the cable length
appropriate?
•
Is the
communications
cable of the
recommended
specification?
The host master
has not been
started.
Check that EtherCAT
Master Unit is operating
correctly. If using an
OMRON EtherCAT
Master Unit, check the
EtherCAT Master Unit
mode and Slave Unit
node addresses. If
using EtherCAT Master
Unit from another
manufacturer, refer to
the user's manual for
that Master Unit.
A hardware failure
occurred.
If the problem is not
resolved even after the
measures described
above are taken, the
Slave Unit hardware
may be damaged.
Replace the applicable
Slave Unit.
Summary of Contents for GX-AD0471
Page 3: ...GX series EtherCAT Slave Units User s Manual Revised October 2018...
Page 4: ......
Page 42: ...2 EtherCAT Slave Unit 2 8 GX series EtherCAT Slave Unit User s Manual...
Page 66: ...4 Installation and Wiring 4 18 GX series EtherCAT Slave Unit User s Manual...
Page 84: ...5 EtherCAT Communications 5 18 GX series EtherCAT Slave Unit User s Manual...
Page 98: ...6 Basic Specifications of Slave Units 6 14 GX series EtherCAT Slave Unit User s Manual...
Page 178: ...7 Digital I O Slave Unit 7 80 GX series EtherCAT Slave Unit User s Manual...
Page 206: ...8 Analog I O Slave Unit 8 28 GX series EtherCAT Slave Unit User s Manual...
Page 280: ...11 Expansion Unit 11 20 GX series EtherCAT Slave Unit User s Manual...
Page 388: ...A Appendix A 84 GX series EtherCAT Slave Unit User s Manual...
Page 392: ...Revision 2 GX series EtherCAT Slave Unit User s Manual...
Page 393: ......