12 - 17
12 Troubleshooting and Maintenance
GX-series EtherCAT Slave Unit User’s Manual
12-
1 T
rou
blesh
oo
ting
12
12-
1-4 Sysmac Er
ror
S
tatus C
odes
Event name
Non-volatile Memory Checksum Error
Event code
14A00000 hex
Meaning
An error occurred in the control parameters.
Source
EtherCAT Master Function Module
Source details
Slave
Detection
timing
When
establishing
communications
after turning ON
power to the
Slave Unit
Error attributes
Level
Minor fault
Recovery
Error reset (after
cycling Slave Unit
power)
Log category
System
Effects
User program
Continues
Operation
The Slave Unit’s I/O communications stop and the outputs
turn OFF.
LED
EtherCAT NET RUN
EtherCAT NET ERR
EtherCAT LINK/ACT
---
Flashes at 1-s intervals.
---
System-defined
variables
Variable
Data type
Name
None
---
---
Cause and
correction
Assumed cause
Correction
Prevention
Noise
Return the control parameters to their
default settings using restore
parameters (1011 hex) of the
EtherCAT Slave Unit.
Implement noise countermeasures.
Attached
information
None
Precautions/
Remarks
The emergency error code is 6330 hex.
Event name
Switch Setting Error
Event code
24610000 hex
Meaning
The setting switch is set out of range.
Source
EtherCAT Master Function Module
Source details
Slave
Detection
timing
When
establishing
communications
after turning ON
power to the
Slave Unit
Error attributes
Level
Minor fault
Recovery
Error reset (after
cycling Slave Unit
power)
Log category
System
Effects
User program
Continues
Operation
The Slave Unit’s I/O communications stop and the outputs
turn OFF.
LED
EtherCAT NET RUN
EtherCAT NET ERR
EtherCAT LINK/ACT
OFF
Flashes at 1-s intervals.
---
System-defined
variables
Variable
Data type
Name
None
---
---
Cause and
correction
Assumed cause
Correction
Prevention
The analog range that is set on the
switch is outside the setting range.
Make sure that switch settings are
within the specified range.
Make sure that switch settings are
correct.
Attached
information
None
Precautions/
Remarks
The emergency error code is 5600 hex.
Summary of Contents for GX-AD0471
Page 3: ...GX series EtherCAT Slave Units User s Manual Revised October 2018...
Page 4: ......
Page 42: ...2 EtherCAT Slave Unit 2 8 GX series EtherCAT Slave Unit User s Manual...
Page 66: ...4 Installation and Wiring 4 18 GX series EtherCAT Slave Unit User s Manual...
Page 84: ...5 EtherCAT Communications 5 18 GX series EtherCAT Slave Unit User s Manual...
Page 98: ...6 Basic Specifications of Slave Units 6 14 GX series EtherCAT Slave Unit User s Manual...
Page 178: ...7 Digital I O Slave Unit 7 80 GX series EtherCAT Slave Unit User s Manual...
Page 206: ...8 Analog I O Slave Unit 8 28 GX series EtherCAT Slave Unit User s Manual...
Page 280: ...11 Expansion Unit 11 20 GX series EtherCAT Slave Unit User s Manual...
Page 388: ...A Appendix A 84 GX series EtherCAT Slave Unit User s Manual...
Page 392: ...Revision 2 GX series EtherCAT Slave Unit User s Manual...
Page 393: ......