A Appendix
A - 8
GX-series EtherCAT Slave Unit User’s Manual
*1 This object is supported by unit version 1.2 or later of the GX-series Digital I/O Slave Units, Analog I/O Slave
Units, and Encoder Input Slave Units.
*2 Can be used only with the GX-ILM08C.
•
This object gives the diagnosis history. This object is used to enable or disable emergency
messages.
•
Sub-index 1 (Maximum Messages) gives the number of error messages.
•
Sub-index 2 (Newest Messages) gives the sub-index number the latest message in the diagnosis
history.
•
Sub-index 3 (Newest Acknowledged Message) is the number of the newest acknowledged message.
The operation differs as described below during reading and writing.
The following is for the GX-series Digital I/O Slave Units, Analog I/O Slave Units, and Encoder Input
Slave Units.
10F3 hex
Diagnosis History
Sub-index 0: Number of entries
Range:
−
Unit:
−
Default: 0D hex
Attribute:
−
Size: 1 byte (U8)
Access: RO
PDO map: Not possible
Sub-index 1: Maximum Messages
Range:
−
Unit:
−
Default: 00 hex
Attribute:
−
Size: 1 byte (U8)
Access: RO
PDO map: Not possible
Sub-index 2: Newest Message
Range:
−
Unit:
−
Default:
−
Attribute:
−
Size: 1 byte (U8)
Access: RO
PDO map: Not possible
Sub-index 3: Newest Acknowledged Message *1
Range:
−
Unit:
−
Default: 00 hex
Attribute:
−
Size: 1 byte (U8)
Access: RW
PDO map: Not possible
Sub-index 4: New Messages Available *1
Range: FALSE, TRUE
Unit: -
Default: FALSE
Attribute: -
Size: 1 bite
Access: RO
PDO map: Possible
Sub-index 5: Flags
Range: 0000 hex- 0001 hex
Unit:
−
Default: 0000 hex
Attribute:
−
Size: 2 bytes (U16)
Access: RW
PDO map: Not possible
Sub-index 6 to 13: Diagnosis Message 1-8
Range:
−
Unit:
−
Default:
−
Attribute:
−
Size: 23 bytes (VS)
Access: RO
PDO map: Not possible
Sub-index 14 to 69: Diagnosis Message 9-64 *2
Range:
−
Unit:
−
Default:
−
Attribute:
−
Size: 23 bytes (VS)
Access: RO
PDO map: Not possible
Read/Write
Operation
Read
•
The subindex of the newest diagnosis history is returned (06 hex to 0D hex).
•
If there are no records in the diagnosis history, 00 hex is returned.
Write
•
Write the number of the diagnosis history between 06 and 0D hex.
•
The value of subindex 04 hex (Newest Messages Available) changes to FALSE.
•
If you write 00 hex, the entire diagnosis history is cleared.
•
If you write values other than 00 hex and 06 to 0D hex, the abort code is returned.
•
If you write a subindex that does not have a diagnosis history, the abort code is returned.
Summary of Contents for GX-AD0471
Page 3: ...GX series EtherCAT Slave Units User s Manual Revised October 2018...
Page 4: ......
Page 42: ...2 EtherCAT Slave Unit 2 8 GX series EtherCAT Slave Unit User s Manual...
Page 66: ...4 Installation and Wiring 4 18 GX series EtherCAT Slave Unit User s Manual...
Page 84: ...5 EtherCAT Communications 5 18 GX series EtherCAT Slave Unit User s Manual...
Page 98: ...6 Basic Specifications of Slave Units 6 14 GX series EtherCAT Slave Unit User s Manual...
Page 178: ...7 Digital I O Slave Unit 7 80 GX series EtherCAT Slave Unit User s Manual...
Page 206: ...8 Analog I O Slave Unit 8 28 GX series EtherCAT Slave Unit User s Manual...
Page 280: ...11 Expansion Unit 11 20 GX series EtherCAT Slave Unit User s Manual...
Page 388: ...A Appendix A 84 GX series EtherCAT Slave Unit User s Manual...
Page 392: ...Revision 2 GX series EtherCAT Slave Unit User s Manual...
Page 393: ......