PART 2: CX-Server PLC Tools
OMRON
CHAPTER 10 – Data Links
CX-Server PLC Tools_ Page 103
No. Item
Function
(4)
Start Address
Area 1 start address
Area 2 start address
(5)
Size
Area 1 local node send size (in words)
Area 2 local node send size (in words)
(6)
Status
Data link status memory area (See note.)
(7) Ordered
Destination
Nodes
Node Refresh Sequence
Beginning with the data link start address above, specify which nodes are to
have data refreshed at the local node address and the order in which data is to
be refreshed (i.e., the node refresh sequence). This order will be the same for
Area 1 and Area 2.
(For the local node address, data is sent from the local node area. For a
remote node address, data is received from the remote node address to the
local area.)
Note:
•
The local node must be included in the refresh nodes.
•
If the address of any node participating in the data links is not entered
here, data will not be received from that node.
Example: If 1, 2, 3 is input, node addresses 1, 2, and 3 will be allocated in
order, beginning with the start address.
(8)
Make Default
Click this button to make the values set for the above items the default values
for new data link settings.
(9)
Next >>
Click to proceed to the next dialog box.
Note:
The default setting for data link status depends on the PLC being used. For details, refer to the
Controller Link Units Operation Manual
(W309).
PLC
Data link status
CS/CJ Series
CVM1/CV Series
The data link status is contained in the 16 words (fixed) from CIO 1500 +25
×
unit 7
to 22 in the CPU Bus Unit Area.
15
8 7
0
+7 words
Node 2
Node 1
... ...
...
+22 words Node 32
Node 31
C200HX/HG/HE
The data link status for node addresses 1 to 6 only is contained in the words from SR 239 to
SR 241, and SR 241 to SR 245.
Network 0 Network 1 15
8 7
0
SR 239
SR 243
Node 2
Node 1
SR 240
SR 244
Node 4
Node 3
SR 241
SR 245
Node 6
Node 5
CQM1H Series
The data link status for node addresses 1 to 6 only is contained in the words from IR 91 to IR
93.
15
8 7
0
IR 91
Node 2
Node 1
IR 92
Node 4
Node 3
IR 93
Node 6
Node 5
7 Set node address 01 as shown in the following table, and then click the
Next
button or press the
Enter
key. Set
node addresses 02 and 03 in the same way.
Item Data
set
Description
Node address
1
−
PLC type
CS1G-CPU45
−
Memory area
CIO
Start address
1000
Sets CIO 1000 as the data link start
address for the Area 1 local node.
Area 1
Send size
30
Sets 30 words as the send size (unit:
words) for the Area 1 local node.
Memory area
D
Start address
500
Sets D00500 as the data link start
address for the Area 2 local node.
Area 2
Send size
30
Sets 30 words as the send size (unit:
words) for the Area 2 local node.
Summary of Contents for CX-PROGRAMMER V9
Page 1: ...Cat No W446 E1 12 CX Programmer Ver 9 CXONE AL_C V4 AL_D V4 SYSMAC OPERATION MANUAL...
Page 2: ......
Page 3: ...SYSMAC CX Programmer Ver 9 CXONE AL C V4 AL D V4 Operation Manual Revised July 2010...
Page 4: ......
Page 6: ......
Page 32: ......
Page 33: ...PART 1 CX Programmer...
Page 34: ......
Page 91: ......
Page 111: ......
Page 191: ...PART 1 CX Programmer CHAPTER 4 Reference OMRON CX Programmer _Page 108...
Page 217: ......
Page 233: ......
Page 234: ...PART 2 CX Server PLC Tools...
Page 235: ......
Page 243: ......
Page 249: ......
Page 261: ...PART 2 CX Server PLC Tools CHAPTER 2 PLC Memory Component OMRON CX Server PLC Tools_Page 18...
Page 280: ......
Page 333: ......
Page 377: ......
Page 409: ......
Page 430: ......
Page 431: ...PART 3 CX Server Runtime...
Page 432: ......
Page 476: ......
Page 482: ......
Page 498: ......
Page 524: ......
Page 534: ......
Page 535: ......
Page 536: ......