PART 2: CX-Server PLC Tools
CHAPTER 3 – IO Table Component
OMRON
CX-Server PLC Tools_Page 30
Note:
It is also possible to edit the Inner Board software switches for the CS/CJ series PLC if
fitted by selecting
Inner Board Software Switches
option from the PLC’s context menu.
The Software Switch dialog is displayed allowing the network unit system memory area to be configured and
transferred to the PLC. Software switches can be defined for the following:
♦
SYSMAC LINK
. Allows set up of Data Link (on/off) and Internode Test (on/off) and setting of response
monitor time;
♦
SYSMAC NET
. Allows set up of Data Link (on/off) and Internode Test; (on/off);
♦
Ethernet
. Allows set up of Internode Test (on/off) and setting of response monitor time.
♦
Controller Link
. Allows the polling status of the node to be set (whether it is a polling or polled unit) and
whether to clear the Controller Link unit EPROM.
Use the following procedure to edit the Software Switch Setup.
1, 2, 3…
1. Highlight the rack/unit in the IO Table tree.
2. Click the right-mouse button and select
Software Switches
.
3. Set the required software switch setup options for the specified rack/unit.
General
The
General
tab of the Software Switches dialog provides the complete software switches settings for a Basic unit,
PC unit, Mini-map unit, Host Link unit, Motion Control unit, ME-Net unit, DeviceNet Master unit and ISO Baud
unit. It also serves as partial software switches settings for other units.
1, 2, 3…
1. Access the Software Switch dialog for an appropriate rack/unit.
2. Set the required CIO and DM area address in the
CIO Address
field and
DM Address
field.
Data Link Area
The
Data Link
tab is used to control whether Data Link is generated automatically or by a specific Data Link table
for SYSMAC LINK, SYSMAC NET and Controller Link. This setup is only used if the Node Type is Master. The
list box at the bottom of the chapter is only used when Data Link is set to one of the automatic options (i.e. not
specific).
1, 2, 3…
1. Select
Transfer from PLC
from the
Options
menu to transfer the current system area
settings from the unit.
2. Select the required unit and click the right-mouse button. Select the
Software Switches
setting.
3. Adjust the settings as required.
4. Select
Transfer to PLC
from the
Options
menu to transfer the network parameters to the
unit.
5. Select
the
Reset Unit
setting to restart the unit - the written settings are activated in the unit.
Note:
If the unit which is being set is the one on which the current communication to the PLC
is being made, the PLC needs to be closed and opened before communications can
continue.
Ethernet
The Ethernet setup differs from SYSMAC LINK, SYSMAC NET and Controller Link by not having a Data Link
Area setup and by having two further dialog boxes, the IP Address Table and IP Router Table. This particular
interface requires that each device attached to the network has an IP address, and that routing information for
directing data across the network is also included (where necessary); such address information ensures that data is
transmitted correctly between two nodes.
Note:
Table information is only used if the
IP Address Conv.
Method radio button is not set to
Auto
.
The File Transfer Protocol (FTP) allows access to a file card on the PLC. If a FTP login name and password are
entered then these are used to start an FTP session. For more information, refer to the Ethernet User’s Manual.
The IP Address Table
dialog allows the IP address of a network node to be entered.
1, 2, 3…
1. Select the Ethernet Unit from the IO Table and click the right-mouse button.
2. Select
the
Unit Setup
option.
Summary of Contents for CX-PROGRAMMER V9
Page 1: ...Cat No W446 E1 12 CX Programmer Ver 9 CXONE AL_C V4 AL_D V4 SYSMAC OPERATION MANUAL...
Page 2: ......
Page 3: ...SYSMAC CX Programmer Ver 9 CXONE AL C V4 AL D V4 Operation Manual Revised July 2010...
Page 4: ......
Page 6: ......
Page 32: ......
Page 33: ...PART 1 CX Programmer...
Page 34: ......
Page 91: ......
Page 111: ......
Page 191: ...PART 1 CX Programmer CHAPTER 4 Reference OMRON CX Programmer _Page 108...
Page 217: ......
Page 233: ......
Page 234: ...PART 2 CX Server PLC Tools...
Page 235: ......
Page 243: ......
Page 249: ......
Page 261: ...PART 2 CX Server PLC Tools CHAPTER 2 PLC Memory Component OMRON CX Server PLC Tools_Page 18...
Page 280: ......
Page 333: ......
Page 377: ......
Page 409: ......
Page 430: ......
Page 431: ...PART 3 CX Server Runtime...
Page 432: ......
Page 476: ......
Page 482: ......
Page 498: ......
Page 524: ......
Page 534: ......
Page 535: ......
Page 536: ......