121
For the controller that can’t receive the serial data output through PS
terminal, the absolute encoder data is transmitted to the controller in
the form of incremental pulses through the output of the EA and EB
terminals, which are the incremental encoder output signals in the
early stage. Among the absolute value data, 1 revolution data is
transmitted after the multi-revolution data.
The serial data of the absolute value can be received through the
EA
and EB
terminals in the following order.
1. Keep /ABS-DT signal at low level, 10 ms or more.
2. Clear the UP/DOWN counter that counts the incremental pulses to 0 so that
it can be ready for the absolute encoder data reception.
3. Receive the multi-revolution data transmitted from the drive after 100 ms.
4. The EA and EB of the drive starts working with ordinary incremental
encoder output signals 50 ms after they transmitted 1 revolution data.
Encoder Signal
Signal
Status
Pulse
EA
During initialization when the power is ON
Early Incremental Pulse
During ordinary operation after initialization
Incremental Pulse
EB
During initialization when the power is ON
Early Incremental Pulse
During ordinary operation after initialization
Incremental Pulse
EC
Always
Origin Pulse
PS
Always
Serial Data of absolute encoder
Summary of Contents for CSDP Plus
Page 1: ...Maximum Value for OEMs SM CSDP Plus Servo Drive User Manual...
Page 16: ...18...
Page 30: ...32 Higher Control Connector CN1 Circuit Diagram...
Page 33: ...35 Compact Absolute Encoder Wiring Serial Encoder Wiring...
Page 38: ...40...
Page 120: ...122...
Page 179: ...181 Speed Torque Curve...
Page 180: ...182...
Page 183: ...185 Speed Torque Curve...
Page 184: ...186...
Page 187: ...189...
Page 190: ...192 Speed Torque Curve...
Page 193: ...195...
Page 196: ...198...
Page 201: ...203...
Page 204: ...206...
Page 207: ...209...
Page 210: ...212...
Page 215: ...217...
Page 230: ...232...
Page 252: ...254...
Page 253: ......