Please set the scale of the analog monitor channel
1 at SEt-08. The setting range is 1 to 65535 /V and
the default value is 500.
Please set the scale of the analog monitor channel
2 at SEt-09. The setting range is 1 to 65535 /V and
the default value is 500.
If the scale of the analog monitor channel 1 is set to 500 of the speed
command (0), the speed command of the controller that corresponds
to the monitor output 1V is 500 RPM. Since the maximum output is 10
V, the speed can be monitored up to 5000 RPM. Therefore, the
monitoring range of the overall speed command is ±5000 RPM.
If the scale of the analog monitor channel 2 is 1000 of the position
command (2), the position command of the controller that
corresponds to the monitor output of 1V is 1000 pulses. As the
maximum output is 10 V, the position command can be checked up to
10000 pulses. Therefore, the monitoring range of the overall position
command is
±
10000 pulses..