223
CHAPTER 8 FUNCTIONS
8
8.
3 T
e
mperat
ure Cont
rol
M
ode
(2) Remote I/O signals, remote registers, and remote buffer memory areas that
can be used
The following table lists the remote I/O signals, remote registers, and remote buffer memory areas that can be
used with this function. (The table below shows the correspondences between the terminals used and the remote
I/O signals/remote registers/remote buffer memory areas.)
(3) Setting method
1.
Set "Method selection" to "Param write" of the control mode to be used.
"CC IE Field Configuration" window
Select the temperature control module from "List of
stations"
[CC IE Field Configuration]
[Online]
[Parameter Processing of Slave Station]
2.
Set "CH
Temperature conversion setting".
●
When heating-cooling control (expanded mode) or mix control (expanded mode) is selected, "CH
Temperature
conversion setting" is ignored.
●
When the setting for the Temperature conversion setting is changed from "0: Not used" to "1: Use", temperature
conversion starts. The completion of the first temperature conversion does not turn on CH
Operation monitor (RX11 to
RX14).
Item name
Remote I/O signal, remote register, remote buffer memory
Reference
MT2 (CH2)
MT3 (CH3)
MT4 (CH4)
CH
Operation monitor
RX12
RX13
RX14
CH
Sensor two-point correction offset latch completion
RX28
RX2A
RX2C
CH
Sensor two-point correction gain latch completion
RX29
RX2B
RX2D
CH
Sensor two-point correction offset latch request
RY28
RY2A
RY2C
CH
Sensor two-point correction gain latch request
RY29
RY2B
RY2D
CH
Alert definition
RWr5
RWr6
RWr7
CH
Temperature process value (PV)
RWr9
RWrA
RWrB
CH
Input range
130H
160H
190H
CH
Primary delay digital filter setting
13DH
16DH
19DH
CH
Temperature conversion setting
1C1H
1C2H
1C3H
Sensor correction function selection
1E4H
Cold junction temperature compensation selection
1E9H
CH
Sensor correction value setting
281H
282H
283H
CH
Sensor two-point correction offset value (measured
value)
288H
28CH
290H
CH
Sensor two-point correction offset value (corrected
value)
289H
28DH
291H
CH
Sensor two-point correction gain value (measured
value)
28AH
28EH
292H
CH
Sensor two-point correction gain value (corrected
value)
28BH
28FH
293H
Cold junction temperature process value
600H
Control switching monitor
602H
CH
Decimal point position
621H
622H
623H
Error code
A00H
Summary of Contents for NZ2GF2B-60TCRT4