289
APPENDICES
A
Appendix
1 Det
ails of
Rem
ot
e I
/O
S
ignals
Appendix
1.
1 Rem
ot
e
input
signals
(10)CH
Alert occurrence flag (RX18 to RX1B)
When an alert occurs, the alert definition is stored in CH
Alert definition (RWr4 to RWr7), and this signal turns
on.
For conditions where this signal turns off, refer to the following.
The following table lists the signals and remote register areas corresponding to each channel.
Ex.
Time chart for CH1
(a) Condition where CH
Alert occurrence flag (RX18 to RX1B) turns off
The conditions differ depending on the setting of CH
Stop mode setting (address: 118H, 148H, 178H, 1A8H).
Channel
Alert occurrence flag
ON/OFF status
Alert definition
CH1
RX18
OFF: An alert does not occur.
ON: An alert occurs.
RWr4
CH2
RX19
RWr5
CH3
RX1A
RWr6
CH4
RX1B
RWr7
CH
Stop mode setting (address: 118H, 148H,
178H, 1A8H)
Condition where CH
Alert occurrence flag (RX18 to RX1B) turns off
Stop (0)
When either of the following conditions is met
• The cause of an alert was eliminated.
• The module shifted from operating status to stop status (when CH
Operation monitor (RX11 to
RX14) turned off).
Monitor (1)
Alert (2)
The cause of an alert was eliminated.
Standard
Heating-cooling
OFF
ON
0
Detected alert definition
CH1 Alert occurrence
flag (RX18)
CH1 Alert definition (RWr4)
Controlled by the temperature control module