150
(b) Heating-cooling control
The module operates as follows outside the range of CH
Adjustment sensitivity (dead band) setting (address:
111H, 141H, 171H, 1A1H).
(c) Three-position control
Three-position control can also be performed by setting a dead band.
For details, refer to the following.
(d) Setting method
1.
Set "Method selection" to "Param write" of the control mode to be used.
"CC IE Field Configuration" window
Select the temperature control module from "List of
stations"
[CC IE Field Configuration]
[Online]
[Parameter Processing of Slave Station]
2.
Set "CH
Proportion belt_P_setting_CH
heating proportion belt" to 0.0%.
Condition
Heating transistor output
status
Cooling transistor output
status
The temperature process value (PV) is below the lower limit of the
adjustment sensitivity (dead band).
ON
OFF
The temperature process value (PV) is above the upper limit of the
adjustment sensitivity (dead band).
OFF
ON
Temperature
process value (PV)
Time
Adjustment sensitivity
(dead band)
Heating output
(L1H)
Cooling output
(L1C)
Set value (SV)
OFF
ON
ON
OFF