146
(2) Selectable control mode
A control mode can be selected from five modes.
1.
Set "Method selection" to "Param write (Station parameter)".
"CC IE Field Configuration" window
Select the temperature control module from "List of
stations"
[CC IE Field Configuration]
[Online]
[Parameter Processing of Slave Station]
2.
Set any one of "0: Standard control", "1: Heating/Cooling control (Normal mode)", "2:
Heating/Cooling control (Expanded mode)", "3: Mix Control (Normal mode)", and "4: Mix Control
(Expanded mode)" to "Control mode switching".
Control for each channel is as follows.
*1
Only temperature measurement using a temperature input terminal can be performed. (
*2
Heating-cooling control is performed using an output module in the system. (
Immediately after "Control mode switching" is changed, an error (error code: 000DH) occurs. To recover from the error
status, turn on and off Set value backup instruction (RY15) and register the setting after the change to the temperature
control module.
Control mode
Contents
Number of control loops
Standard control
Performs the standard control of four channels.
Standard control 4 loops
Heating-cooling control (normal
mode)
Performs the heating-cooling control. CH3 and CH4 cannot be used.
Heating-cooling control 2 loops
Heating-cooling control (expanded
mode)
Performs the heating-cooling control. The number of loops is expanded using an output
module and others in the system.
Heating-cooling control 4 loops
Mix control (normal mode)
Performs the standard control and the heating-cooling control. CH2 cannot be used.
Standard control 2 loops
Heating-cooling control 1 loop
Mix control (expanded mode)
Performs the standard control and the heating-cooling control. The number of loops is
expanded using an output module in the system.
Standard control 2 loops
Heating-cooling control 2 loops
Channel
Standard control
Heating-cooling control
Mix control
Normal mode
Expanded mode
Normal mode
Expanded mode
CH1
Standard control
Heating-cooling control
Heating-cooling control
Heating-cooling control
Heating-cooling control
CH2
Standard control
Heating-cooling control
Heating-cooling control
Heating-cooling control
CH3
Standard control
Heating-cooling
control
Standard control
Standard control
CH4
Standard control
Heating-cooling
control
Standard control
Standard control