229
CHAPTER 8 FUNCTIONS
8
8.
4 CC-Link I
E
F
ield
N
e
tw
ork
F
unct
ion
8.4.3
CC-Link IE Field Network diagnostic function
With this function, whether any network error occurs or not can be checked through the engineering tool connected to
the CPU module.
(1) How to use
The following instructions assume the use of GX Works2 as the engineering tool.
1.
Connect GX Works2 to the CPU module.
2.
Start CC-Link IE Field Network diagnostics from the menu of GX Works2.
[Diagnotics]
[CC IE Field Diagnotics]
Item to be diagnosed
Description
Reference
1)
Display of network
configuration diagram and
error status
The status of the CC-Link IE Field Network can be checked.
When an error arises or a warning is issued from the temperature control module, the status of
the station is indicated on the icon.
User's manual for
the master/local
module used
2)
Display of selected-station
status and error details
The communication status of the station selected in "Network Status" can be checked.
3)
Communication Test
The transient communication route and whether the communication is established from the
connected station to the destination station can be checked.
IP Communication Test
The reaching time and the route of the IP communication from the connected station to the target
station can be checked. This function is unavailable for the temperature control module.
Cable Test
The cable status between the connected station and the destination station can be checked.
Link Start/Stop
The network data link can be started and stopped.
4)
Network Event History
The history of various events that occurred in the network can be checked. This function is
unavailable for the temperature control module.
Reserved Station Function
Enable
A reservation for a station can be temporarily cancelled, and the cancellation can be disabled.
Also, the station numbers for the modules set as reserved stations can be checked on a list.
Enable/Disable Ignore Station
Errors
A station not set as an error invalid station can be temporarily set as an error invalid station, and
the error invalid station setting can be disabled. Also, the station numbers for the modules set as
(temporarily) error ignore stations can be checked on a list.
5)
System Monitor
The system monitor on the selected station is activated and the status of the module can be
checked.
This function is unavailable for the temperature control module.
Remote Operation
The selected station can be reset through the remote operation.
Page 230, Section
8.4.3 (1) (a)
Common
2)
1)
3)
4)
5)