91
CHAPTER 6 INSTALLATION AND WIRING
6
6.
4
W
iring wit
h a
T
e
rminal B
lock
fo
r M
odule P
o
wer
Supply
and F
G
6.4
Wiring with a Terminal Block for Module Power Supply
and FG
(1) Tightening torque
Tighten the terminal block screws within the following specified torque range. Tightening the screws too much
may damage the module case.
(2) Wire to be used
The following table describes the wire to be connected to the terminal block for module power supply and FG.
(3) Installing and removing the terminal block
To remove the terminal block, loosen the terminal block fixing screw with a slotted screwdriver.
To install the terminal block, tighten the terminal block fixing screw.
Failure to secure the terminal block may cause drop, short circuit, malfunction.
Screw type
Tightening torque range
Terminal block mounting screw (M2.5 screw)
0.2 to 0.3N
m
Terminal screw (M2.5 screw)
0.5 to 0.6N
m
Diameter
Type
Material
Temperature rating
20 to 16 AWG
Stranded
Copper
75
or more