213
CHAPTER 8 FUNCTIONS
8
8.
3 T
e
mperat
ure Cont
rol
M
ode
(b) Setting for the dead band
To prevent an error alert of loop disconnection detection, set a non-alert band (temperature band in which the
loop disconnection is not detected) where the set value (SV) is at the center. If the temperature process value
(PV) is within the loop disconnection detection dead band, an alert is not output even though the alert
conditions of loop disconnection are met.
1.
Set "Method selection" to "Param write" of the control mode to be used.
"CC IE Field Configuration" window
Select the temperature control module from "List of
stations"
[CC IE Field Configuration]
[Online]
[Parameter Processing of Slave Station]
2.
Set "CH
Loop disconnection detection dead band".
If this function is not necessary, set 0 to "CH
Loop disconnection detection dead band".