(64)MAN mode (address: 601H)
This area is for checking completion of the mode shift when shifting AUTO (auto) mode to MAN (manual) mode.
The following values are stored in this remote buffer memory area.
• 0: MAN mode shift uncompleted
• 1: MAN mode shift completed
The following figure shows bits of the remote buffer memory area that correspond to each channel.
When shift to MAN mode is completed, bits corresponding to appropriate channel become MAN mode shift
completed (1).
(a) How to shift the mode
Shift the mode by the following remote buffer memory area.
• CH
AUTO/MAN mode shift (address: 113H, 143H, 173H, 1A3H) (
(b) Setting manipulated value (MV) in MAN mode
Set the manipulated value (MV) in the following remote buffer memory area.
• CH
MAN output setting (address: 114H, 144H, 174H, 1A4H) (
Set the manipulated value (MV) after confirming MAN mode (address: 601H) has become MAN mode shift
completed (1).
(65)Control switching monitor (address: 602H)
The value set in Control mode shift (address: 80H) is stored. The mode in operation can be confirmed.
The following table lists the stored values and the contents.
Select a mode with Control mode shift (address: 80H).
For details, refer to the following.
For details on the modes, refer to the following.
Page 138, Section 8.2, Page 145, Section 8.3.1
Stored value
Control mode
0H
Temperature control mode
Standard Control
1H
Heating-cooling control (normal mode)
2H
Heating-cooling control (expanded mode)
3H
Mix control (normal mode)
4H
Mix control (expanded mode)
100H
Temperature input mode
Standard
Heating-cooling
b15
0
b14
0
b13
0
b12
0
b11
0
b10
0
b9
0
b8
0
b7
0
b6
0
b5
0
b4
0
b3
CH4
b2
CH3
b1
CH2
b0
CH1
Bit data from b4 to b15 are fixed to 0.
Common