332
(21)CH
Manual reset amount setting (address: 112H, 142H, 172H, 1A2H)
Set the amount of the proportional band (P) to be moved.
For details on the manual reset function, refer to the following.
(a) Setting range
Set the value within the range -1000 to 1000 (-100.0% to 100.0%) of the full scale of the set input range. For
details on the input range, refer to the following.
The setting range is the same between the standard control and heating-cooling control.
(b) Enabling the setting
Enable the setting contents by either of the following.
• Turning off and on Initial data setting request flag (RY9) while the operations of all channels are stopped
• Turning off and on During operation setting change instruction (RY10)
(c) Default value
The default values are set to 0 (0.0%) in all channels. The default value is the same between the standard
control and the heating-cooling control.
(22)CH
AUTO/MAN mode shift (address: 113H, 143H, 173H, 1A3H)
Select whether to calculate the manipulated value (MV) by PID operation or to set it manually by the user.
(a) Setting range
(b) When AUTO mode is shifted to MAN mode
The following operation is performed.
• The manipulated value (MV) calculated by PID operation is transferred to CH
MAN output setting
(address: 114H, 144H, 174H, 1A4H). (For preventing a rapid change of the manipulated value (MV))
• When the shift to the MAN mode is completed, bits of the corresponding channel of MAN mode (address:
601H) are set to MAN mode shift completed (1).
Set the manipulated value (MV) in MAN mode after confirming completion of the mode shift.
Setting value
Setting
contents
Description
0
AUTO
Activates the AUTO mode. The manipulated value (MV) calculated by PID operation is used to calculate the ON time of
the control cycle.
1
MAN
Activates the MAN mode. The manipulated value (MV) written in CH
MAN output setting (address: 114H, 144H, 174H,
1A4H) is used to calculate the ON time of the control output cycle.
Standard
Heating-cooling
Standard
Heating-cooling
AUTO/MAN mode
AUTO mode
MAN mode
MAN mode shift
uncompleted (0)
MAN mode shift
uncompleted (0)
AUTO (0)
AUTO (0)
MAN (1)
MAN mode shift
completed (1)
AUTO mode
CH□ AUTO/MAN mode shift
(address: 113H, 143H, 173H, 1A3H)
MAN mode
(address: 601H)
Controlled by the temperature control module
Summary of Contents for NZ2GF2B-60TCRT4
Page 2: ......
Page 86: ...84 Memo ...
Page 268: ...266 Memo ...
Page 377: ...375 APPENDICES A Appendix 6 External Dimensions Memo ...
Page 383: ...I 4 4 7 8 381 Memo ...
Page 387: ......