157
CHAPTER 8 FUNCTIONS
8
8.
3 T
e
mperat
ure Cont
rol
M
ode
8.3.5
Manual control
Manual control is a form of control for which the user sets the manipulated value (MV) manually instead of obtaining it
automatically by PID control.
The manipulated value (MV) is checked every 250ms or 500ms
*1
, and is reflected to transistor output.
*1
This value differs depending on the setting under "Sampling cycle selection". (
(1) Setting method
Follow the following procedure for setting.
1.
Shift to the MAN (manual) mode. (Set MAN (1) in CH
AUTO/MAN mode shift (address: 113H,
143H, 173H, 1A3H).) (
2.
Check that MAN mode shift completed (1) is stored in MAN mode (address: 601H). (
3.
Set the manipulated value (MV) in CH
MAN output setting (address: 114H, 144H, 174H, 1A4H)
*1
.
(
*1
The setting range differs for standard control and heating-cooling control. In standard control: -50 to 1050 (-5.0 to
105.0%) In heating-cooling control: -1050 to 1050 (-105.0 to 105.0%)
Standard
Heating-cooling