320
(8) CH
Integral time (I) setting (address: 103H, 133H, 163H, 193H)
Set integral time (I) to perform PID control.
(a) Setting range
The setting range is 0 to 3600 (0 to 3600s).
(b) In the P control or PD control
Set this setting to 0.
For details on control methods, refer to the following.
(c) Enabling the setting
Enable the setting contents by either of the following.
• Turning off and on Initial data setting request flag (RY9) while the operations of all channels are stopped
• Turning off and on During operation setting change instruction (RY10)
(d) Default value
The default values are set to 240 (240s) in all channels.
(9) CH
Derivative time (D) setting (address: 104H, 134H, 164H, 194H)
Set derivative time (D) to perform PID control.
(a) Setting range
The setting range is 0 to 3600 (0 to 3600s).
(b) In the P control or PI control
Set this setting to 0.
For details on control methods, refer to the following.
(c) Enabling the setting
Enable the setting contents by either of the following.
• Turning off and on Initial data setting request flag (RY9) while the operations of all channels are stopped
• Turning off and on During operation setting change instruction (RY10)
(d) Default value
The default values are set to 60 (60s) in all channels.
Common
Common