298
(7) CH
Stop request flag (RY18 to RY1B)
Turn on this signal to stop operation in a channel.
• If this signal is turned on during the operation of temperature control module, operation is stopped for the
corresponding channel and CH
Operation monitor (RX11 to RX14) turns off. (The operation is stopped
according to the setting of CH
Stop mode setting (address: 118H, 148H, 178H, 1A8H).) Check that CH
Operation monitor (RX11 to RX14) is off, and turn off the signal.
• If the signal is turned on during the temperature control module stop, the module remains stopped (CH
Operation monitor (RX11 to RX14) remains off). An error or an alarm is not output.
• If the signal is turned on while CH
Operation request flag (RY11 to RY14) is on, an error occurs (error
code: 001
H).
Common
OFF
OFF
OFF
ON
ON
CH□ Stop request flag
(RY18 to RY1B)
Module status
CH□ Operation monitor
(RX11 to RX14)
Operating
Stop
Controlled by the program
Controlled by the temperature control module
OFF
OFF
OFF
ON
ON
ON
CH□ Operation request flag
(RY11 to RY14)
Module status
CH□ Operation monitor
(RX11 to RX14)
CH□ Stop request flag
(RY18 to RY1B)
Latest error code (RWr0)
Stop
Operation shift
processing
Operating
0000H
001□H
Controlled by the program
Controlled by the temperature control module
Summary of Contents for NZ2GF2B-60TCRT4
Page 2: ......
Page 86: ...84 Memo ...
Page 268: ...266 Memo ...
Page 377: ...375 APPENDICES A Appendix 6 External Dimensions Memo ...
Page 383: ...I 4 4 7 8 381 Memo ...
Page 387: ......