348
(45)CH
Alert set value 1 (address: 224H, 22CH, 234H, 23CH)
, CH
Alert set value 2 (address: 225H, 22DH, 235H, 23DH)
, CH
Alert set
value 3 (address: 226H, 22EH, 236H, 23EH)
, CH
Alert set value 4
(address: 227H, 22FH, 237H, 23FH)
Set temperature values where CH
Alert 1 (b8 of RWr4 to RWr7) to CH
Alert 4 (b11 of RWr4 to RWr7) turn on
according to selected alert mode of alert 1 to 4.
For CH
Alert definition (RWr4 to RWr7), refer to the following.
For details on the alert function, refer to the following.
(a) Alert mode
Set the alert mode of alert 1 to 4 in the following remote buffer memory areas. Each alert mode for alert 1 to 4
corresponds to alert set value 1 to 4.
(b) Setting range
The setting range differs depending on the setting of the following remote buffer memory area. (each full scale
differs)
• CH
Input range (address: 100H, 130H, 160H, 190H) (
Also, the setting range differs depending on alert mode to be set. (
Page 348, Appendix 3 (45) (a))
When a value which is out of the setting range is set, a write data error (error code: 0004H) and the following
situations occur.
• Error flag (RXA) turns on.
• The error code is stored to Latest error code (RWr0).
(c) Setting unit
The value to be set differs depending on the stored value in CH
Decimal point position (address: 620H,
621H, 622H, 623H). (
• No decimal place (0): Set a value in 1
(
or digit) unit.
• One decimal place (1): Set a value in 0.1
(
) unit (tenfold value).
Remote buffer memory
Remote buffer memory address
Reference
CH1
CH2
CH3
CH4
CH
Alert 1 mode setting
220H
228H
230H
238H
CH
Alert 2 mode setting
221H
229H
231H
239H
CH
Alert 3 mode setting
222H
22AH
232H
23AH
CH
Alert 4 mode setting
223H
22BH
233H
23BH
Alert mode
Setting range of alert set value
Remarks
No alert
Upper limit input alert, lower limit input alert
Temperature measurement range of the
input range
Same as with standby
Upper limit deviation alert, lower limit deviation alert, upper limit
deviation alert (using the set value (SV)), lower limit deviation alert
(using the set value (SV))
(-(full scale)) to full scale
Same as with standby and standby
(second time)
Upper lower limit deviation alert, within-range alert, upper lower limit
deviation alert (using the set value (SV)), within-range alert (using the
set value (SV))
0 to full scale
Same as with standby and standby
(second time)
Standard
Heating-cooling
Standard
Heating-cooling
Standard
Heating-cooling
Standard
Heating-cooling