(c) When performing auto tuning
Set to AUTO (0). If MAN (1) is set, the auto tuning is not performed.
(d) Enabling the setting
Enable the setting contents by either of the following.
• Turning off and on Initial data setting request flag (RY9) while the operations of all channels are stopped
• Turning off and on During operation setting change instruction (RY10)
(e) Default value
The default values are set to AUTO (0) in all channels.
(23)CH
MAN output setting (address: 114H, 144H, 174H, 1A4H)
This remote buffer memory area is used for setting the manipulated value (MV) in the MAN mode.
(a) How to shift the mode
Shift the mode by the following remote buffer memory area.
• CH
AUTO/MAN mode shift (address: 113H, 143H, 173H, 1A3H) (
(b) Setting range
The setting range is different between the standard control and the heating-cooling control.
• In standard control: -50 to 1050 (-5.0 to 105.0%)
• In heating-cooling control: -1050 to 1050 (-105.0 to 105.0%)
(c) Enabling the setting
Enable the setting contents by either of the following.
• Turning off and on Initial data setting request flag (RY9) while the operations of all channels are stopped
• Turning off and on During operation setting change instruction (RY10)
Make sure the corresponding bit of MAN mode (address: 601H) has been set to 1 (ON) and write a value in the
MAN output setting. A value that is written when the corresponding bit of MAN mode (address: 601H) is 0
(OFF) will be replaced with the manipulated value (MV) calculated by PID operation by the system.
(d) Default value
The default values are set to 0 (0.0%) in all channels.
Standard
Heating-cooling