(c) Manual control
The following table lists Enable/Disable of the setting.
For details on the manual control, refer to the following.
(d) Enabling the setting
Enable the setting contents by either of the following.
• Turning off and on Initial data setting request flag (RY9) while the operations of all channels are stopped
• Turning off and on During operation setting change instruction (RY10)
(e) Default value
The following table lists the default value of each remote buffer memory area.
Remote buffer memory
Enable/Disable of the setting in the
manual control
Remarks
CH
Upper limit output limiter (address:
105H, 135H, 165H, 195H)
Enable
When an output exceeds the upper limit output limiter value, the
manipulated value (MV) of the manual control is fixed (clipped) to the
upper limit output limiter value that is set. When an output falls below
the lower limit output limiter value, the manipulated value (MV) of the
manual control is fixed (clipped) to the lower limit output limiter value
that is set.
CH
Lower limit output limiter (address:
106H, 136H, 166H, 196H)
CH
Heating upper limit output limiter
(address: 105H, 135H, 165H, 195H)
Disable
CH
Cooling upper limit output limiter
(address: 1C5H, 1CAH, 1CFH, 1D4H)
Remote buffer memory
Default value
CH
Upper limit output limiter (address: 105H, 135H, 165H, 195H)
1000 (100.0%)
CH
Lower limit output limiter (address: 106H, 136H, 166H, 196H)
0 (0.0%)
CH
Heating upper limit output limiter (address: 105H, 135H, 165H, 195H)
1000 (100.0%)
CH
Cooling upper limit output limiter (address: 1C5H, 1CAH, 1CFH, 1D4H)