(d) Default value
The default values are set to 0 in all channels.
This setting can not only be set manually but also be calculated automatically. Automatic calculation is performed when the
simultaneous temperature rise AT (auto tuning) or self-tuning (when the automatic calculation of the temperature rise
parameter is set) is normally completed.
(61)CH
Simultaneous temperature rise dead time (address: 2D2H, 2D6H, 2DAH,
2DEH)
Set Simultaneous temperature rise dead time (time taken for the temperature to start rising after the output is
turned on).
For details on the simultaneous temperature rise function, refer to the following.
(a) Setting range
The setting range is 0 to 3600 (s).
(b) Enabling the setting
Enable the setting contents by either of the following.
• Turning off and on Initial data setting request flag (RY9) while the operations of all channels are stopped
• Turning off and on During operation setting change instruction (RY10)
(c) Default value
The default values are set to 0 in all channels.
This setting can not only be set manually but also be calculated automatically. Automatic calculation is performed when the
simultaneous temperature rise AT (auto tuning) or self-tuning (when the automatic calculation of the temperature rise
parameter is set) is normally completed.