169
CHAPTER 8 FUNCTIONS
8
8.
3 T
e
mperat
ure Cont
rol
M
ode
8.3.11
Alert function
When the temperature process value (PV) or deviation (E) reaches the value set in advance, the system is set in an
alert status. Use this function to activate danger signals of devices or safety devices.
The alert function is classified into input alerts and deviation alerts depending on the setting of the alert mode.
• Input alert: upper limit input alert, lower limit input alert (
• Deviation alert: upper limit deviation alert, lower limit deviation alert, upper lower limit deviation alert, within-
range alert (
(1) Input alert
With the upper limit input alert, when the temperature process value (PV) is equal to or greater than the alert set
value, the system is put in an alert status.
With the lower limit input alert, when the temperature process value (PV) is equal to or less than the alert set
value, the system is put in an alert status.
(a) Setting method
Set the alert mode. (
• Upper limit input alert: Set the alert mode to "1: Upper limit input alert".
• Lower limit input alert: Set the alert mode to "2: Lower limit input alert".
Upper limit input alert
Lower limit input alert
Standard
Heating-cooling
Non-alert status
Alert status
Time
Temperature process value (PV)
Alert status
Alert set value
Non-alert status
Alert status
Time
Temperature process value (PV)
Alert status
Alert set value
Summary of Contents for NZ2GF2B-60TCRT4
Page 2: ......
Page 86: ...84 Memo ...
Page 268: ...266 Memo ...
Page 377: ...375 APPENDICES A Appendix 6 External Dimensions Memo ...
Page 383: ...I 4 4 7 8 381 Memo ...
Page 387: ......