The temperature control module constantly monitors the control state. When the control system is oscillatory, this
function allows PID constants to be automatically changed under the following situations such as: After the control has
been just started, When the set value (SV) is changed, and When the characteristics of a controlled object fluctuates.
Unlike the auto tuning function, a normal control response waveform is monitored and PID constants are automatically
calculated and set. This allows an object to be controlled with the most suitable PID constants all the time without
disturbance.
(1) Differences between auto tuning and self-tuning
The following table lists the differences between auto tuning and self-tuning.
Item
Auto tuning
Self-tuning
PID constants calculation
The manipulated value (MV) is turned on/off and PID constants
are calculated based on the hunting cycle and amplitude of the
temperature process value (PV) for the set value (SV).
PID constants are calculated based on an oscillation occurred
under situations such as after the control has been just started,
the set value (SV) has been changed, and when a control
response is oscillatory.
Execution method
Turning off and on CH
Auto tuning instruction (RY20 to RY23)
starts auto tuning and changes PID constants upon completion.
The temperature control module constantly monitors the
control response. PID constants are calculated and changed
when the control response is slow.
Control response
PID constants are calculated based on the control response of
when the manipulated value (MV) is turned on/off; therefore, the
control may become unstable.
PID constants are calculated based on the control response
during temperature control; therefore, the control is stable.
Calculation result
The optimum PID constants are calculated by one tuning.
In the standard control, CH
Loop disconnection detection
judgment time (address: 116H, 146H, 176H, 1A6H) is also
calculated.
The optimum PID constants may not be obtained by one
tuning. CH
Loop disconnection detection judgment time
(address: 116H, 146H, 176H, 1A6H) is not calculated.
PID constants setting
when the characteristics
of a controlled object
fluctuate
Users perform auto tuning again to change PID constants.
The temperature control module automatically changes PID
constants.
Available control mode
The standard control and heating-cooling control
The standard control only
Standard