(2) Sensor two-point correction function
With this function, the difference between the temperature process value (PV) and the actual temperature
between the two points selected in advance (a corrected offset value and a corrected gain value) is stored. Based
on this gradient, the difference between a sensor and the actual temperature is corrected.
Carry out a sensor two-point correction when CH
Operation monitor (RX11 to RX14) is off. In addition, set CH
Stop mode setting (address: 118H, 148H, 178H, 1A8H) to Monitor (1).
Before
correction
Input temperature
Temperature
process value (PV)
After
correction
CH□ Sensor two-point correction gain value
(corrected value)
(address: 287H, 28BH, 28FH, 293H)
CH□ Sensor two-point correction offset value
(corrected value)
(address: 285H, 289H, 28DH, 291H)
CH□ Sensor two-point correction offset value (measured value)
(address: 284H, 288H, 28CH, 290H)
CH□ Sensor two-point correction gain value
(measured value)
(address: 286H, 28AH, 28EH, 292H)