8.3.21
Proportional band setting function
Proportional band (P) values can be set for heating and cooling separately using this function. Different gradients can
be set by using different proportional band (P) values in a heating and cooling area.
(1) Setting method
(a) For heating
1.
Set "Method selection" to "Param write" of the control mode to be used.
"CC IE Field Configuration" window
Select the temperature control module from "List of
stations"
[CC IE Field Configuration]
[Online]
[Parameter Processing of Slave Station]
2.
Set "CH
Proportion belt_P_setting_CH
heating proportion belt".
(b) For cooling
1.
Set "Method selection" to "Param write" of the control mode to be used.
"CC IE Field Configuration" window
Select the temperature control module from "List of
stations"
[CC IE Field Configuration]
[Online]
[Parameter Processing of Slave Station]
2.
Set "CH
Cooling proportion belt_Pc_setting".
Heating-cooling
100%
0%
-100%
Manipulated value
for cooling (MVc) 100%
Manipulated value
for heating (MVh) 0%
Manipulated value
for heating (MVh) 100%
Manipulated value
for cooling (MVc) 0%
Set value (SV)
Heating proportional
band (Ph)
Cooling
Heating
Cooling proportional
band (Pc)
Narrowing only cooling
proportional band (Pc)
is also possible.
Manipulated value
for heating (MVh)
Manipulated value
for cooling (MVc)