344
(39)Resolution of the manipulated value for output with another analog module
(address: 1E8H)
Set the resolution of the following remote registers. (
• CH
Manipulated value (MV) (RWr10 to RWr13)
• CH
Manipulated value for heating (MVh) (RWr10 to RWr13)
• CH
Manipulated value for cooling (MVc) (RWr14 to RWr17)
For details, refer to the following.
(a) Setting range
• 0: 0 to 4000
• 1: 0 to 12000
• 2: 0 to 16000
• 3: 0 to 20000
The manipulated value (MV) reflecting the resolution is stored in the following remote registers. (
• CH
Manipulated value (MV) for output with another analog module (RWr18 to RWr1B)
• CH
Manipulated value of heating (MVh) for output with another analog module (RWr18 to RWr1B)
• CH
Manipulated value of cooling (MVc) for output with another analog module (RWr1C to RWr1F)
(b) Enabling the setting
To enable the setting, turn off and on Initial data setting request flag (RY9) while the operations of all channels
are stopped.
(c) Default value
The default value is set to 0 to 4000 (0).
(40)Cold junction temperature compensation selection (address: 1E9H)
Select the method of the cold junction temperature compensation.
(a) Supported modules
Only NZ2GF2B-60TCTT4 can be used.
(b) Setting range
• 0: Use Standard Terminal Block
• 1: Use prohibited
• 2: Not use cold junction temperature compensation
(c) Enabling the setting
Enable the setting contents by either of the following.
• Turning off and on Initial data setting request flag (RY9) while the operations of all channels are stopped
• Turning off and on During operation setting change instruction (RY10)
(d) Default value
The default value is set to Use Standard Terminal Block (0).
Standard
Heating-cooling
Common