182
(2) Output
Instead of the transistor output from the temperature control module, analog output values from other analog
modules (such as a D/A converter module) can be used as the manipulated value (MV).
(a) Setting method (for the standard control)
1.
Set "Method selection" to "Param write" of the control mode to be used.
"CC IE Field Configuration" window
Select the temperature control module from "List of
stations"
[CC IE Field Configuration]
[Online]
[Parameter Processing of Slave Station]
2.
Select the value on "Manipulated value resolution switching for output with another analog
module".
3.
Store the value in CH
Manipulated value (MV) for output with another analog module (RWr18 to
RWr1B) into the buffer memory in other analog module (such as a D/A converter module).
●
When the manipulated value (MV) is -5.0% to 0.0%, 0 is stored in Manipulated value (MV) for output with another analog
module. When the manipulated value (MV) is 100.0% to 105.0%, 4000/12000/16000/20000 is stored in Manipulated
value (MV) for output with another analog module.
●
The manipulated value (MV) in a percentage value is stored into Manipulated value (MV) for output with another analog
module (digital output value) in real time.
Summary of Contents for NZ2GF2B-60TCRT4
Page 2: ......
Page 86: ...84 Memo ...
Page 268: ...266 Memo ...
Page 377: ...375 APPENDICES A Appendix 6 External Dimensions Memo ...
Page 383: ...I 4 4 7 8 381 Memo ...
Page 387: ......