292
(13)CH
Simultaneous temperature rise status (RX24 to RX27)
The execution state of the simultaneous temperature rise can be monitored with this signal.
• OFF: Simultaneous temperature rise not in process
• ON: Simultaneous temperature rise in process
During control with the simultaneous temperature rise function, this signal turns to Simultaneous temperature rise
in process (ON).
The following figure shows the timing when the signal turns to Simultaneous temperature rise not in process
(OFF). (In the figure, CH1 and CH2 are set to group 1. (
The signal does not turn to Simultaneous temperature rise not in process (OFF) at the completion of the
temperature rise. As in the figure above, the temperature is raised to a certain point with the simultaneous
temperature rise function, and the signal remains Simultaneous temperature rise in process (ON) for that interval.
After that the temperature is raised with the PID constants of each channel, and the signal turns to Simultaneous
temperature rise not in process (OFF).
For details on the simultaneous temperature rise function, refer to the following.
Standard
ON
OFF
ON
OFF
OFF
ON
OFF
CH1 Set value (SV)
The temperature rise
completion times are
matched.
Temperature is raised with
the PID constants of each
channel for this interval.
Temperature is raised with
the simultaneous
temperature rise function
for this interval.
Temperature
process value (PV)
Time
CH2 Set value (SV)
Temperature rise start point
Group 1
arrival point
CH1 Simultaneous temperature
rise status (RX24)
and
CH2 Simultaneous temperature
rise status (RX25)
CH1 Temperature rise
judgment flag (RX1C)
and
CH2 Temperature rise
judgment flag (RX1D)
CH□ Operation monitor
(RX11 to RX14)
Controlled by the temperature control module