Alert definition (RWr4 to RWr7)
Bits corresponding to alerts detected in each channel become 1.
*1
For the temperature measurement range, refer to the following.
Bit data from b6 to b15 become Unused in the temperature input mode.
(a) Temperature measurement range
The temperature measurement range is as follows.
• (Input range lower limit - 5% of full scale) to (Input range upper limit + 5% of full scale)
Ex.
Calculation for the case when CH
Input range (address: 100H, 130H, 160H, 190H) is 38 and the
temperature measurement range is -200.0 to 400.0
• Input range lower limit - 5% of full scale = -200 - ((400.0 - (-200.0))
0.05) = -230.0
• Input range upper limit + 5% of full scale = 400 + ((400.0 - (-200.0))
0.05) = 430.0
Therefore, the temperature measurement range is -230.0 to 430.0
.
The temperature control module checks whether the input temperature is within temperature measurement
range of the input range. If the input temperature is out of the temperature measurement range, CH
Input
range upper limit (b0 of RWr4 to RWr7) or CH
Input range lower limit (b1 of RWr4 to RWr7) turns to 1 (ON).
The conditions which the temperature control module uses to judge whether the measured temperature is
within the temperature measurement range or not differ depending on the following settings.
• CH
Stop mode setting (address: 118H, 148H, 178H, 1A8H) (
Target bit number
Flag name
Alert definition
b0
CH
Input range upper limit
Temperature process value (PV) has exceeded the temperature measurement range
of the set
input range.
b1
CH
Input range lower limit
Temperature process value (PV) has fallen below the temperature measurement range
of the set
input range.
b2
CH
Process alarm upper limit
Temperature process value (PV) has reached the process alarm upper upper limit value or more.
b3
CH
Process alarm lower limit
Temperature process value (PV) has reached the process alarm lower lower limit value or lower.
b4
CH
Rate alarm upper limit
The variation of temperature process value (PV) has reached the rate alarm upper limit value or
more.
b5
CH
Rate alarm lower limit
The variation of temperature process value (PV) has reached the rate alarm lower limit value or
lower.
b6 to b7
(fixed to 0)
(Unused)
b8
CH
Alert 1
Alert 1 has occurred. (
b9
CH
Alert 2
Alert 2 has occurred. (
b10
CH
Alert 3
Alert 3 has occurred. (
b11
CH
Alert 4
Alert 4 has occurred. (
b12
(fixed to 0)
(Unused)
b13
CH
Loop disconnection
detection
Loop disconnection has been detected. (
b14
(fixed to 0)
(Unused)
b15
(fixed to 0)
(Unused)
Common
b15
b2
b1
b0
b5
b4
b3
b7
b6
b8
b9
b10
b11
b12
b13
b14
0
0
0
Bit data b15 is
fixed to 0.
Bit data from b6 to
b7 are fixed to 0.