37
CHAPTER 3 SPECIFICATIONS
3
3.
2 Per
form
ance Spec
ificat
io
ns
(b) NZ2GF2B-60TCRT4
The following table lists the types of platinum resistance thermometer that can be used with the NZ2GF2B-
60TCRT4 and temperature measurement range.
(2) Sampling cycle and control output cycle
This section describes the sampling cycle and control output cycle of the temperature control module.
(a) Sampling cycle
The temperature control module performs PID operations in the order of CH1, CH2, CH3, CH4, CH1, CH2 .....
The time from when PID operation is started on the current channel (CHn) until PID operation is restarted on
the current channel (CHn) is called a sampling cycle. Select 250ms or 500ms as a sampling cycle.
• Sampling cycle selection (address: 1H. b12) (
The number of used channels and the settings of unused channels do not affect the sampling cycle.
(b) Control output cycle
The control output cycle is the ON/OFF cycle of transistor output.
The manipulated value (MV) represents the ON time of the control output cycle in percentage.
Set the control output cycle in the following remote buffer memory area in the range of 1 to 100s (or 0.5 to
100.0s).
• CH
Control output cycle setting (address: 10CH, 13CH, 16CH, 19CH) (
In the heating-cooling control, the following remote buffer memory areas are used for the manipulated value
(MV) and control output cycle.
Platinum resistance
thermometer type
Temperature measurement
range
Resolution
Temperature measurement
range
Resolution
Pt100
-200.0 to 850.0
-200.0 to 600.0
-200.0 to 200.0
0.1
-300 to 1100
1
-300.0 to 300.0
0.1
JPt100
-200.0 to 640.0
-200.0 to 500.0
-200.0 to 200.0
0.1
-300 to 900
1
-300.0 to 300.0
0.1
Data type
Target
Reference
Manipulated value (MV)
CH
Manipulated value for heating (MVh) (RWr10 to RWr13)
CH
Manipulated value for cooling (MVc) (RWr14 to RWr17)
Control output cycle
CH
Heating control output cycle setting (address: 10CH, 13CH, 16CH, 19CH)
CH
Cooling control output cycle setting (address: 1C6H, 1CBH, 1D0H, 1D5H)
Sampling cycle
Sampling cycle
CH1 PID
operation
CH2 PID
operation
CH3 PID
operation
CH4 PID
operation
CH1 PID
operation
CH2 PID
operation
OFF
ON
ON
OFF
Control output cycle
Control output cycle
Transistor output
Summary of Contents for NZ2GF2B-60TCRT4
Page 2: ......
Page 86: ...84 Memo ...
Page 268: ...266 Memo ...
Page 377: ...375 APPENDICES A Appendix 6 External Dimensions Memo ...
Page 383: ...I 4 4 7 8 381 Memo ...
Page 387: ......