310
(b) Setting change rate limiter setting (address: 1H. b1)
With this setting, the change rate of the set value (SV) per time unit in cases when the set value (SV) is
changed can be set. Select "batch" setting or "individual" setting for the variation limiter set value at
temperature rise and drop.
• 0: Disable (Temperature rise/Temperature drop batch setting) (default)
• 1: Enable (Temperature rise/Temperature drop individual setting)
For details, refer to the following.
• Setting change rate limiter setting function (
(c) Control output cycle unit selection setting (address: 1H. b2)
The control output cycle is the ON/OFF cycle of transistor output for the temperature control function.
The control output cycle is set in the following remote buffer memory areas.
• CH
Control output cycle setting (address: 10CH, 13CH, 16CH, 19CH) (standard control)
• CH
Heating control output cycle setting (address: 10CH, 13CH, 16CH, 19CH) (heating control)
• CH
Cooling control output cycle setting (address: 1C6H, 1CBH, 1D0H, 1D5H) (heating-cooling control)
The unit of the above control output cycle can be selected from 1s or 0.1s using this bit.
The following shows the setting values.
• 0: 1s cycle (default)
• 1: 0.1s cycle
For details, refer to the following.
• Control output cycle unit selection function (
(d) Moving averaging process setting (address: 1H. b3)
Moving averaging process setting is the function to enable/disable the moving averaging process.
The following shows the setting values.
• 0: Enable (default)
• 1: Disable
For details, refer to the following.
• Moving averaging process to a temperature process value (PV) (
(e) Sampling cycle selection (address: 1H. b12)
The sampling cycle is the time period from the instant when a conversion starts on a channel to the instant
when the next conversion starts on the same channel.
The following shows the setting values.
• 0: 500ms/4CH
• 1: 250ms/4CH (default)
For details, refer to the following.
• Sampling cycle (
When the setting of Sampling cycle selection (address: 1H. b12) is changed, the remote buffer memory areas of address
100H and the following addresses are overwritten to their default value.
Also, an error (error code: 000FH) occurs immediately after the setting of Sampling cycle selection (address: 1H. b12) is
changed. To eliminate the error, turn on and off Set value backup instruction (RY15), and register a newly set parameter to
the non-volatile memory.
Summary of Contents for NZ2GF2B-60TCRT4
Page 2: ......
Page 86: ...84 Memo ...
Page 268: ...266 Memo ...
Page 377: ...375 APPENDICES A Appendix 6 External Dimensions Memo ...
Page 383: ...I 4 4 7 8 381 Memo ...
Page 387: ......