158
8.3.6
Control output cycle unit selection function
The unit of the control output cycle can be selected from 1s or 0.1s using this function.
When the control output cycle is set in 0.1s, control can be more attentive.
The control output cycle is the ON/OFF cycle of transistor output for the temperature control function.
The cycle can be set in the following parameter setting screen.
(1) Setting method
1.
Set "Method selection" to "Param write (Station parameter)".
"CC IE Field Configuration" window
Select the temperature control module from "List of
stations"
[CC IE Field Configuration]
[Online]
[Parameter Processing of Slave Station]
2.
Set "Control output cycle unit switching setting".
An error (error code: 000EH) occurs right after changing this setting. To recover from the error status, turn on and off Set
value backup instruction (RY15) and register the setting after the change to the temperature control module.
Control mode
Item
Standard control
CH
Control output cycle setting
Heating-cooling control
CH
Heating control output cycle setting
CH
Cooling control output cycle setting
Standard
Heating-cooling
Summary of Contents for NZ2GF2B-60TCRT4
Page 2: ......
Page 86: ...84 Memo ...
Page 268: ...266 Memo ...
Page 377: ...375 APPENDICES A Appendix 6 External Dimensions Memo ...
Page 383: ...I 4 4 7 8 381 Memo ...
Page 387: ......