306
(9) CH
Self-tuning flag (RWr14 to RWr17)
The execution state of self-tuning can be monitored in this area.
For details on the self-tuning function, refer to the following.
The following contents are stored in each bit.
• 0: OFF
• 1: ON
Bit
Flag name
Condition on which a flag turns to 1 (ON)
Condition on which a flag turns to 0 (OFF)
b0
PID auto-correction status
This flag turns to 1 (ON) when PID constants are
corrected by the self-tuning.
This flag turns to 0 (OFF) when any of the following
operations was performed.
• The corresponding channel shifted from operating
status to stop status (when CH
Operation monitor
(RX11 to RX14) turned off).
• Do not run the ST (0) is set to CH
Self-tuning setting
(address: 2C0H to 2C3H).
This flag also turns to 0 (OFF) in the following cases.
• When the self-tuning has started by the change of the
set value (SV)
• When the temperature process value (PV) moved out of
the stable condition and the vibration ST has started
b1
Simultaneous temperature
rise parameter correction
status
This flag turns to 1 (ON) when simultaneous
temperature rise parameter
has been corrected
by self-tuning.
b2 to b7
(fixed to 0)
(Unused)
b8
Self-tuning disable status
This flag turns to 1 (ON) when the self-tuning was
not able to be executed.
This flag turns to 0 (OFF) when any of the following
operations was performed.
• The corresponding channel shifted from operating
status to stop status (when CH
Operation monitor
(RX11 to RX14) turned off).
• Do not run the ST (0) is set to CH
Self-tuning setting
(address: 2C0H to 2C3H).
This flag also turns to 0 (OFF) when all causes of the self-
tuning disable were eliminated.
For the causes, refer to the following.
Standard
b15
b2
b1
b0
b10
b9
b8
b7
0
0
0
0
0
0
0
0
0
0
0
Fixed to 0
Fixed to 0
to
to