(a) How to set the primary delay digital filter
In "CH
Primary delay filter setting", set the time until the temperature process value (PV) changes by 63.3%
(time constant).
1.
Set "Method selection" to "Param write" of the control mode to be used.
"CC IE Field Configuration" window
Select the temperature control module from "List of
stations"
[CC IE Field Configuration]
[Online]
[Parameter Processing of Slave Station]
2.
Set "CH
Primary delay filter setting".
Ex.
When 3 (3s) is set in "Primary delay filter setting"
The temperature reaches 256.3
which is 63.3% of the temperature process value (PV) three seconds
after the temperature input value has reached 250.0
.
0
3
250.0
252.0
254.0
256.0
258.0
260.0
262.0
Temperature input value
Temperature process value (PV)
Elapsed time (s)
Temperature input value ( )